Plan Review Notes
Plan Review Notes For Permit 19081341
Permit Number 19081341
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-05 17:08:1209/05/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE
 REQUIRED AT THE WATER METER PER THE CITY OF WEST PALM
 CROSS CONNECTION CONTROL MANUAL AND A PVB FOR POOL FILL
 PER THE CITY OF WEST PALM BEACH ORD #2853-95 AND 2017
 FBC-PLUMBING SEC.608.1. A PERMIT REQUIRED BY A LICENSED
 CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES PRIOR TO
 FINAL INSPECTION SO PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS.
  
 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 3. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1.
  
 4. PLEASE PROVIDE DOCUMENT GAS AND SPA HEATERS THAT
 SHOW IT HAVING A MINIMUM THERMAL EFFICIENCY OF 82 % FOR
 HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN
 TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL HEATERS
 FIRED BY NATURAL OR LP GAS SHALL NOT HAVE CONTINUOUSLY
 BURNING PILOT LIGHTS. 2017 FBC-ENERGY ? SEC. R403.10.4.
  
 5. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC-
 ENERGY- SEC. R 403.10.3.
  
 6. SEPARATE PERMIT REQUIRED FOR GAS PER WPB AMENDMENTS
 TO THE FBC SEC. 105.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  