| Date |
Text |
| 2019-08-27 07:18:55 | 8/27/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE - |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413.4.1. |
| | |
| | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017 |
| | FBC FUEL GAS RES. SEC. G2413.2. |
| | |
| | 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| | SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| | THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413. |
| | |
| | 4) GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.3.5.3 (12) RESIDENTIAL GAS |
| | |
| | 5) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8, |
| | 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4, |
| | G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 6) THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL |
| | GAS RES. SEC. G2413.3 |
| | |
| | 8) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9) TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 11) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| | INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| | |
| | 12) ALL GAS AND SPA HEATERS SHALL HAVE A MINIMUM |
| | THERMAL EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON |
| | OR AFTER APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH |
| | ANSI Z 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS |
| | SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2017 |
| | FBC-ENERGY ? SEC. R403.10.4 |
| | |
| | 13) TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE |
| | THE COST OF ALL EQUIPMENT INCLUDING POOL HEATER. |
| | PROVIDE BONA FIDE SIGNED CONTRACT PER WPB AMENDMENTS TO |
| | THE FBC 109.3 |
| | |
| | 14) HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY |
| | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| | OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC- |
| | ENERGY- SEC. R 403.10.3. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |