Plan Review Notes
Plan Review Notes For Permit 19081275
Permit Number 19081275
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-16 15:52:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A. PER FBC ACC 213.3.6, THE BATHROOM SHOWER, ONE OF THE
 TWO FOAT TANK ROOMS AND THE OPEN FLOAT TUB ROOM SHALL
 COMPLY WITH FBC ACC 608.
  
 1) PROVIDE CLEAR FLOOR SPACE ON PLAN VIEW SHOWING
 COMPLIANCE WITH FBC ACC SECTION 305.
 2) PROVIDE A DETAIL (ELEVATION) OF THE SHOWER SHOWING
 COMPLIANCE WITH FBC ACC SECTION 608.
  
 B. WATER CLOSET SHALL BE 16" MINIMUM AND 18" MAXIMUM,
 CENTERLINE TO SIDE WALL PER FBC ACC 604.2 AND THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM TO THE WALL SIDE AND 24 INCHES
 (610 MM) MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2.
 C. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW PER FBC ACC 604.7.
  
 2. WHAT IS THE OPEN FLOAT TUB AND HOW IS WATER SUPPLIED
 TO IT?
 3. HOW ARE THE FLOAT TANKS DRAINED? DO THE HOSE BIBS
 PROVIDE WATER FOR THE FLOAT TANKS?
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION/CUT SHEETS FOR FLOAT TANKS AND OPEN FLOAT
 TUB.
 5. RE: SANITARY ISOMETRIC; A SHOWER IS INDICATED WHERE
 THE OPEN FLOAT TUB SHOULD BE. PLEASE CLARIFY.
 6. SHOW LOCATION OF SHUT OFF VALVES FOR STACKABLE
 WASHER/DRYER COMBO TO SHOW COMPLIANCE WITH FBC PL
 606.3..
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19081275 5612 S DIXIE HWY
  
  