| 2019-09-17 08:59:02 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19081275 |
| | ADD: 5612 S. DIXIE HWY. |
| | CONT: FLORIDA DEVELOPMENT & CONSTRUCTION |
| | TEL: 954-707-1309 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 17/2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE CLARIFY THE SCOPE OF WORK. WITHIN THE |
| | SUBMITTED SET OF PLANS SHEET A.05 HAS NOTES THAT NO |
| | ROOF WORK IS TO BE COMPLETED. NOTES 2 & 3 INDICATE ROOF |
| | TOP A/C IS TO BE REPLACED AND DETAILS ARE FOR THE |
| | FLASHING REPAIRS. ALSO WITH IN THE PERMIT PACKAGE THERE |
| | IS A SET (2) OF MIAMI-DADE NOA?S FOR GAF CONVENTIONAL |
| | BUILT-UP-ROOF SYSTEMS OVER RECOVER DECKS. PLEASE NOTE |
| | THE DESIGNER OF RECORD HAS NOT REVIEWED THIS PRODUCT |
| | APPROVAL, NOR SELECTED ONE OF THE SUB-SYSTEMS FOR |
| | INSTALLATION. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: W. P. B. |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | 2) THE 2017 EXISTING BUILDING CODE SECTION 706.3 DEALS |
| | WITH RECOVERING OF ROOF DECKS. |
| | 706.3 RECOVERING VERSUS REPLACEMENT. NEW ROOF COVERINGS |
| | SHALL NOT BE INSTALLED WITHOUT FIRST REMOVING ALL |
| | EXISTING LAYERS OF ROOF COVERINGS DOWN TO THE ROOF DECK |
| | WHERE ANY OF THE FOLLOWING CONDITIONS OCCUR: |
| | |
| | 2.1. WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER |
| | SOAKED OR HAS DETERIORATED TO THE POINT THAT THE |
| | EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A |
| | BASE FOR ADDITIONAL ROOFING. |
| | |
| | 2.2. WHERE THE EXISTING ROOF COVERING IS WOOD SHAKE, |
| | SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT TILE. |
| | |
| | 2.3. WHERE THE EXISTING ROOF HAS TWO OR MORE |
| | APPLICATIONS OF ANY TYPE OF ROOF COVERING. |
| | |
| | 2.4. WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS |
| | BLISTERS ARE CUT OR SCRAPED OPEN AND REMAINING |
| | MATERIALS SECURED DOWN BEFORE APPLYING ADDITIONAL |
| | ROOFING. |
| | |
| | 2.5. WHERE THE EXISTING ROOF IS TO BE USED FOR |
| | ATTACHMENT FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH |
| | THE SECUREMENT PROVISIONS OF SECTION 1504.1 OF THE |
| | FLORIDA BUILDING CODE, BUILDING CANNOT BE MET. |
| | |
| | IN THE 2017 FBC-B SECTION 1504.1. FBC-B 1504.1 WIND |
| | RESISTANCE OF ROOFS. ROOF DECKS AND ROOF COVERINGS |
| | SHALL BE DESIGNED FOR WIND LOADS IN ACCORDANCE WITH |
| | CHAPTER 16 AND SECTIONS 1504.2, 1504.3 AND 1504.4. |
| | A PULL TEST IS NECESSARY. 1504.3.1 OTHER ROOF SYSTEMS. |
| | BUILT-UP, MODIFIED BITUMEN, FULLY ADHERED OR |
| | MECHANICALLY ATTACHED SINGLE-PLY ROOF SYSTEMS, METAL |
| | PANEL ROOF SYSTEMS APPLIED TO A SOLID OR CLOSELY FITTED |
| | DECK AND OTHER TYPES OF MEMBRANE ROOF COVERINGS SHALL |
| | BE TESTED IN ACCORDANCE WITH FM 4474, UL 580 OR UL |
| | 1897. |
| | |
| | 3) THE CGC STEPHEN CIRIACO IS NOT LICENSED AS A |
| | CERTIFIED ROOFING CONTRACTOR AND THE RESTRICTIONS FOR |
| | THE CGC LICENSE UNDER F. S. 489.113(3)(B) ONLY ALLOWS |
| | FOR: (B) A GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR |
| | SHALL NOT BE REQUIRED TO SUBCONTRACT THE INSTALLATION, |
| | OR REPAIR MADE UNDER WARRANTY, OF WOOD SHINGLES, WOOD |
| | SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE ROOFING |
| | MATERIALS ON A NEW BUILDING OF HIS OR HER OWN |
| | CONSTRUCTION. |
| | |
| | 4) SHEET A.03 PLEASE REVIEW THE FLOAT TANKS, OPEN FLOAT |
| | TUB, SHOWERS AND BATHROOM # 1 WITH SHOWER. |
| | PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE 213.2 |
| | TOILET ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE |
| | PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE |
| | BATHING ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL |
| | COMPLY WITH 603. PLEASE REVIEW THE PLUMBING PLAN |
| | REVIEWER?S COMMENTS THAT DEAL WITH ALL OF THE |
| | ACCESSIBLE ELEMENTS THAT NEED TO SHOW CODE COMPLIANCE. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |