| Plan Review Notes For Permit 19081237 |
| Permit Number |
19081237 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-27 19:01:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MAXIMUM DESIGN PRESSURE OF -52.5 PSF THAT IS | | | SPECIFIED FOR FASTENING OPTION #3 ON PAGE 51 OF NOA | | | NO.18-0919.12 FOR THE GAF MODIFIED ROOF SYSTEM IS NOT | | | ADEQUATE FOR THE CORNER AND PERIMETER AREAS. SUBMIT TWO | | | SETS OF SIGNED AND SEALED RAS117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON PAGE 67. |
|