Plan Review Notes
Plan Review Notes For Permit 19081237
Permit Number 19081237
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-27 19:01:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM DESIGN PRESSURE OF -52.5 PSF THAT IS
 SPECIFIED FOR FASTENING OPTION #3 ON PAGE 51 OF NOA
 NO.18-0919.12 FOR THE GAF MODIFIED ROOF SYSTEM IS NOT
 ADEQUATE FOR THE CORNER AND PERIMETER AREAS. SUBMIT TWO
 SETS OF SIGNED AND SEALED RAS117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON PAGE 67.