| Plan Review Notes For Permit 19081234 |
| Permit Number |
19081234 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-09-25 06:31:20 | 1) SUBMIT TWO COPIES OF A CLEAN SURVEY WITHOUT PREVIOUS | | | STAMPS OR OTHER PERMIT NUMBERS STAMPED ON IT. WPB | | | AMEND. TO FBC SEC. 107.3.5.3. | | | 2) SIZE THE MEDIUM PRESSURE LINE GOING TO THE GENERATOR | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT A COPY OF THE SIZING TABLE FOR THE LOW | | | PRESSURE SIDE OF THE SYSTEM. 2017 FBC-FUEL GAS SEC. | | | 402.3. | | | 4) MY CALCULATIONS FOR THE TOTAL BTU'S ON THE SYSTEM IS | | | 1,110,000 BUT THE SUBMITTED GAS PLAN NOTES 920,000. | | | CLARIFY. | | | 5) SUBMIT TWO COPIES OF PAGES 1, 40 AND 41 OF THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE REGULATORS. THESE | | | PAGES HAVE INSTALLATION INSTRUCTIONS FOR THE REGULATOR | | | AND ITS VENT.\ | | | 6) SHOW THE DISTANCE FROM THE REGULATOR TO EACH | | | APPLIANCE/ PIECE OFEQUIPMENT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|