2019-09-25 06:31:201) SUBMIT TWO COPIES OF A CLEAN SURVEY WITHOUT PREVIOUS
 STAMPS OR OTHER PERMIT NUMBERS STAMPED ON IT. WPB
 AMEND. TO FBC SEC. 107.3.5.3.
 2) SIZE THE MEDIUM PRESSURE LINE GOING TO THE GENERATOR
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT A COPY OF THE SIZING TABLE FOR THE LOW
 PRESSURE SIDE OF THE SYSTEM. 2017 FBC-FUEL GAS SEC.
 402.3.
 4) MY CALCULATIONS FOR THE TOTAL BTU'S ON THE SYSTEM IS
 1,110,000 BUT THE SUBMITTED GAS PLAN NOTES 920,000.
 CLARIFY.
 5) SUBMIT TWO COPIES OF PAGES 1, 40 AND 41 OF THE
 MANUFACTURER'S SPECIFICATIONS FOR THE REGULATORS. THESE
 PAGES HAVE INSTALLATION INSTRUCTIONS FOR THE REGULATOR
 AND ITS VENT.\
 6) SHOW THE DISTANCE FROM THE REGULATOR TO EACH
 APPLIANCE/ PIECE OFEQUIPMENT.
  