| 2019-08-29 11:50:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS ONLY ONE HORN STOBE INDICATED WITH EACH | | | UNIT, WHICH MAY NOT MEET THE DECIBEL LEVELS AT THE | | | PILLOW HEIGHT PER NFPA 72 | | | | | | PER NFPA 72 | | | | | | 18.4.5 SLEEPING AREA REQUIREMENTS. | | | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO | | | PROVIDE | | | SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND | | | LEVEL OF AT | | | LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 | | | DB | | | ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT | | | LEAST | | | 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, | | | WHICHEVER IS | | | GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA | | | REQUIRED TO BE | | | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). | | | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR | | | RETRACTABLE | | | PARTITION, IS LOCATED BETWEEN THE NOTIFICATION | | | APPLIANCE AND | | | THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED | | | WITH THE | | | BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. | | | | | | PLEASE ENUSRE COMPLIANCE AND PROVIDE REVISIONS AS | | | APPLICABLE BEFORE FINAL INSPECTIONS, | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|