2020-01-14 15:54:083RD REVIEW:19081206
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING
 FIXTURE COUNT STATES SEPARATE FACILITIES SHALL NOT BE
 REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A
 TOTAL FLOOR AREA OF 3000SQFT OR LESS THIS IS NOT
 CORRECT THE CODE DOES NOT PROVIDE A EXCEPTIONS USING
 SQFT. PLEASE SEE FBC PL 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 EXCEPTIONS:
  
 1)SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
  
 2)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 STRUCTURES OR TENANT SPACES WITH A TOTAL OCCUPANT LOAD,
 INCLUDING BOTH EMPLOYEES AND CUSTOMERS, OF 15 OR FEWER.
  
 3)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 MERCANTILE OCCUPANCIES IN WHICH THE MAXIMUM OCCUPANT
 LOAD IS 100 OR FEWER.
  
 2. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING
 FIXTURE COUNT STATES BUSINESS 1 WATER CLOSET PER 50
 THIS IS INCORRECT THE CODE IS 1 PER 25 FOR THE FIRST 50
 AND 1
 PER 50 FOR THE REMAINDER EXCEEDING 50 AND THE PLAN
 STATES 1 LAVATORY PER 80 THAT IS INCORRECT THE CODE IS
 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE
 REMAINDER EXCEEDING 80
 PER FBC PL TABLE 403.1
  
 3. SHT. P-1 SANITARY ISOMETRIC DRAWING THE SINKS IN THE
 BREAK ROOM AND EXAM ROOMS 1,2,3 ARE NOT VENTED THEY
 SHALL EACH BE INDIVIDUAL VENTED PER FBC PL 901.2.1
 910.1
  
 4.SHT. P-1 GENERAL EQUIPMENT NOTES DO NOT APPEAR TO
 PERTAIN TO THIS JOB PLEASE REMOVE ANY NOTES FOR KITCHEN
 EQUIPMENT GAS EQUIPMENT AND WALK IN FREEZERS OR ANY
 OTHER NOTE NOT FOR THIS JOB PER WPB AMEND TO FBC
 107.2.1
  
 5. PLEASE SHOW SIZE MANUFACTURE AND MODEL OF THE
 THERMAL EXPANSION TANK ON THE WATER HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 6. SHEET P-2 DETAIL #3 SHOWS 2 DIFFERENT HOT WATER
 RECIRCULATION PUMPS NONE IS SHOWN ON THE ISOMETRIC
 DRAWING OR FLOOR PLAN PLEASE CLARIFY IF A RECIRCULATION
 SYSTEM IS BEING USED SHOW IT ON ALL DRAWING AND PROVIDE
 MANUFACTURE MODEL NUMBER AND INSTILLATION GUIDE AND
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 AND FBC PL
 607.2,607.2.1,
  
 7. THE EXISTING COLD WATER SERVICE FOR THIS UNIT IS NOT
 CLEARLY SHOWN PLEASE CLEARLY SHOW SIZE LOCATION AND
 BACKFLOW DEVISE ONE WILL BE REQUIRED FOR THIS UNIT TO
 SEPARATE IT IF THERE ARE OTHER UNITS ON THE SAME
 SERVICE FROM METER. PER WPB UTILITIES CROSS CONNECTION
 MANUAL
  
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  