| 2020-01-14 15:54:08 | 3RD REVIEW:19081206 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING |
| | FIXTURE COUNT STATES SEPARATE FACILITIES SHALL NOT BE |
| | REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A |
| | TOTAL FLOOR AREA OF 3000SQFT OR LESS THIS IS NOT |
| | CORRECT THE CODE DOES NOT PROVIDE A EXCEPTIONS USING |
| | SQFT. PLEASE SEE FBC PL 403.2 SEPARATE FACILITIES. |
| | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE |
| | FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | EXCEPTIONS: |
| | |
| | 1)SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR |
| | DWELLING UNITS AND SLEEPING UNITS. |
| | |
| | 2)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN |
| | STRUCTURES OR TENANT SPACES WITH A TOTAL OCCUPANT LOAD, |
| | INCLUDING BOTH EMPLOYEES AND CUSTOMERS, OF 15 OR FEWER. |
| | |
| | 3)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN |
| | MERCANTILE OCCUPANCIES IN WHICH THE MAXIMUM OCCUPANT |
| | LOAD IS 100 OR FEWER. |
| | |
| | 2. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING |
| | FIXTURE COUNT STATES BUSINESS 1 WATER CLOSET PER 50 |
| | THIS IS INCORRECT THE CODE IS 1 PER 25 FOR THE FIRST 50 |
| | AND 1 |
| | PER 50 FOR THE REMAINDER EXCEEDING 50 AND THE PLAN |
| | STATES 1 LAVATORY PER 80 THAT IS INCORRECT THE CODE IS |
| | 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE |
| | REMAINDER EXCEEDING 80 |
| | PER FBC PL TABLE 403.1 |
| | |
| | 3. SHT. P-1 SANITARY ISOMETRIC DRAWING THE SINKS IN THE |
| | BREAK ROOM AND EXAM ROOMS 1,2,3 ARE NOT VENTED THEY |
| | SHALL EACH BE INDIVIDUAL VENTED PER FBC PL 901.2.1 |
| | 910.1 |
| | |
| | 4.SHT. P-1 GENERAL EQUIPMENT NOTES DO NOT APPEAR TO |
| | PERTAIN TO THIS JOB PLEASE REMOVE ANY NOTES FOR KITCHEN |
| | EQUIPMENT GAS EQUIPMENT AND WALK IN FREEZERS OR ANY |
| | OTHER NOTE NOT FOR THIS JOB PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 5. PLEASE SHOW SIZE MANUFACTURE AND MODEL OF THE |
| | THERMAL EXPANSION TANK ON THE WATER HEATER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 6. SHEET P-2 DETAIL #3 SHOWS 2 DIFFERENT HOT WATER |
| | RECIRCULATION PUMPS NONE IS SHOWN ON THE ISOMETRIC |
| | DRAWING OR FLOOR PLAN PLEASE CLARIFY IF A RECIRCULATION |
| | SYSTEM IS BEING USED SHOW IT ON ALL DRAWING AND PROVIDE |
| | MANUFACTURE MODEL NUMBER AND INSTILLATION GUIDE AND |
| | SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 AND FBC PL |
| | 607.2,607.2.1, |
| | |
| | 7. THE EXISTING COLD WATER SERVICE FOR THIS UNIT IS NOT |
| | CLEARLY SHOWN PLEASE CLEARLY SHOW SIZE LOCATION AND |
| | BACKFLOW DEVISE ONE WILL BE REQUIRED FOR THIS UNIT TO |
| | SEPARATE IT IF THERE ARE OTHER UNITS ON THE SAME |
| | SERVICE FROM METER. PER WPB UTILITIES CROSS CONNECTION |
| | MANUAL |
| | |
| | |
| | END OF COMMENTS |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |