| 2020-01-15 09:20:44 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19081206 |
| | 1/15/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: THE REVISED AC EQUIPMENT SCHEDULE |
| | INDICATES AN EXISTING 2.5 TON SYSTEM, HOWEVER THE MODEL |
| | NUMBER OF THE AIR HANDLER, THE TOTAL COOLING CAPACITY, |
| | AND THE TOTAL CFMS OF THE UNIT INDICATE IT IS A 3-TON |
| | SYSTEM- PLEASE CORRECT. |
| | |
| | 2) M1: THE MECHANICAL DUCT LAYOUT PLAN INDICATES A |
| | TOTAL OF 657 CFMS TO BE DISTRIBUTED IN THE TENANT SPACE |
| | WHICH DOES NOT APPEAR TO BE CONSISTENT WITH THE 1200 |
| | CFM TOTAL CAPACITY OF THE SYSTEM. IT MAY BE HELPFUL TO |
| | PERFORM A HEAT LOAD CALACULATION FOR THE SPACE USING |
| | MANUAL N- SECTION C403.2.1 FBC EC. |
| | |
| | 3) M1: THE BOXED NOTE SHOWN BY THE AIR CALCULATIONS |
| | INDICATES AN ERV WILL BE INSTALLED, HOWEVER THERE IS NO |
| | ERV SYSTEM SHOWN ON THE PLANS- PLEASE CLARIFY AND REFER |
| | TO SECTION C403.2.7 FBC EC FOR MORE INFORMATION. PLEASE |
| | NOTE THE CALCULATIONS IN THE BOX INDICATE AN RTU AT |
| | 1200 CFMS AND 507 CFMS OF EXHAUST IN THE SPACE WHICH |
| | DOES NOT APPEAR TO CORRECT- THE PLANS ARE SHOWING AN |
| | AHU IN THE CLOSET, AND TWO BATH EXHAUST FANS. PLEASE |
| | PROVIDE EXHAUST FAN SCHEDULES TO VERIFY NTHE 507 CFMS |
| | OF EXHAUST. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |