Plan Review Notes
Plan Review Notes For Permit 19081206
Permit Number 19081206
Review Stop P
Sequence Number 2
Notes
Date Text
2019-11-21 13:57:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW: 19081206
 PLUMBING COMMENTS: DENIED
 NOTE: A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS
 AS REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 1. RE: PLAN SHEET A-1; NOTE AT INFUSION ROOM, EXAM ROOM
 #1 AND BREAK ROOM SINK LOCATIONS READS ADA 36 " H
 COUNTER. TO BE CLEAR, PER FBC ACC 606.3 STATES THAT
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 WPB FBC 107.2.1, REMOVE THE NOTE AT THE THREE SINKS AND
 PROVIDE A NOTE REFLECTING THE REQUIREMENTS OF 606.3,
 REFERENCING THE THREE SINKS. ADDITIONALLY, THE EXISTING
 ADDED NOTE PERTAINING TO THE THREE SINKS AND FBC ACC
 SECTIONS HAS AN APPARENT TYPO; 21202 SHOULD BE 212.2.
 PLEASE CORRECT.
 2. RE: PLAN SHEET A-2, DETAILS 6 AND 7; REGARDING THE
 SHOWER,
 A. THE LAYOUT AS SHOWN DOES NOT FIT THE
 NARRATIVE/REQUIREMENTS OF FBC ACC SECTION 608; IT IS
 SUGGESTED THAT THE DESIGNERS MEET WITH THE BUILDING
 DEPARTMENT TO CONFIRM AN ACCEPTABLE DESIGN THAT WOULD
 PROVIDE COMPLIANCE. PLEASE SEE ADDITIONAL COMMENTS
 BELOW. PLEASE NOTE THAT THE COMMENTS ARE OBSERVATIONS
 AND SHALL NOT BE TAKEN AS CORRECTIONS THAT IF MADE
 WOULD LEAD TO A SATISFACTORY REVIEW FOR COMPLIANCE. IT
 IS THE DESIGNER'S RESPONSIBILITY TO PROVIDE A COMPLIANT
 DESIGN FOR THE SHOWER.
 B. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE.
 C. IT IS NOTED THAT THE SIDE WALL OF THE WATER CLOSET
 WOULD BE THE BACK WALL OF THE SHOWER IF CONSIDERED A
 ROLL-IN SHOWER. THERE IS A MINIMUM SIXTY (60) INCH
 CLEAR SPACE REQUIRED FOR THE LENGTH OF THE SAID BACK
 WALL. PER FBC ACC 608.2.2.1, A 30 INCH (760 MM) WIDE
 MINIMUM BY 60 INCH (1525 MM) LONG MINIMUM CLEARANCE
 (CLEAR FLOOR SPACE) SHALL BE PROVIDED ADJACENT TO THE
 OPEN FACE OF THE SHOWER COMPARTMENT.
 D. A CONTINUOUS GRAB BAR ON THE SAID BACK WALL SHALL BE
 A MAXIMUM OF 6 INCHES FROM THE TWO SIDE WALLS, AS
 PERTAINS TO THE SHOWER.
 E. GRAB BARS ON THE SAID SIDE WALLS SHALL BE A MAXIMUM
 OF 6 INCHES FROM THE SAID BACK WALL, AS PERTAINS TO THE
 SHOWER.
 F. THE ISSUE HERE IS THE WATER CLOSET AT THE FAR END OF
 THE SHOWER SPACE. THE SPACE IN ACCORDANCE WITH THE
 REQUIREMENTS OF FBC ACC 608.2.1 IS SUPPOSED TO BE CLEAR
 FROM SIDE WALL TO SIDE WALL OR IT MAY HAVE A SEAT ON A
 SIDE WALL. IF, THE THOUGHT IS THAT IT COULD DOUBLE AS A
 SEAT, THEN IT WOULD HAVE TO BE SHOWN TO MEET THE
 REQUIREMENTS OF FBC ACC 610.3, 610.3.1, 610.3.2.1 AND
 610.4. NOTE IT SHALL BE ADJACENT TO THE SHOWER
 CONTROLS.
 3. RE: PLAN SHEET A-2, DETAIL 1. PER WPB FBC 107.2.1,
 WATER CLOSET SPACE SHALL COMPLY WITH FBC 2017, NOT
 2010, 604.3.1 ACCESSIBILITY.
 4. RE: PLAN SHEET A-2, DETAILS 2 AND 3; PER FBC ACC
 609.4, GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, NOT TO THE CENTER. THIS IS A
 SECOND REQUEST.
 5. RE: PLAN SHEET A-2, DETAIL 4; PER FBC ACC 606.3, THE
 DRAWING ON THE RIGHT OF THE LAVATORY HAS A DIMENSION OF
 34 INCHES MINIMUM TO THE LIP OF THE LAVATORY; IT SHALL
 BE A MAXIMUM OF 34".
 6. RE: PLAN SHEET A-2, DETAIL 6 AND 7; PER FBC ACC
 604.7, TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES
 (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED
 TO THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
 7. RE: PLAN SHEET A-2, DETAIL 8; PER WPB FBC 107.2.1,
 PROVIDE IN THE DETAIL HOW THE ENTIRE ROOM WILL BE
 SEALED TO COMPLY WITH FBC PL 417.5.2 SHOWER LINING;
 INCLUDE DETAIL FOR SEALING THE WATER CLOSET VERTICAL
 DRAIN PIPE THROUGH THE FLOOR, INTEGRATING IT WITH THE
 LINER.
 8. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOM
 WITH 3" VENT THROUGH THE ROOF. EACH BATHROOM GROUP
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE WET
 VENT IN ACCORDANCE WITH FBC PL 912.1. CONNECT WET VENT
 BETWEEN THE WATER CLOSET AND THE SHOWER TO COMPLY.
 9. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOMS #1
 AND #2. WATER CLOSETS ARE INTEGRALLY TRAPPED FIXTURES.
 PROVIDING A TRAP IN THE ROUGH DRAIN PIPING AS SHOWN ON
 THE ISOMETRIC CONSTITUTES A DOUBLE TRAP AND AS SUCH
 DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC PL909.1.
 PER FBC 107.2.1, ELIMINATE THE TRAP AND PROVIDE A
 VERTICAL WASTE PIPE EXTENDING FROM THE HORIZONTAL
 PIPING TO THE FLOOR FLANGE POINT OF CONNECTION.
 10. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOMS
 #1 AND #2. SHOWER DRAINS IN BATHROOMS SHALL BE PROVIDED
 WITH TRAP SEAL PROTECTION IN ACCORDANCE WITH THE
 REQUIREMENTS OF FBC PL 1002.4.1.
 11. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; PER WPB FBC
 107.2.1, NOTE THAT 3 INCH PIPE DOWN TO FIRST FLOOR
 SANITARY SHALL NOT DISCHARGE THROUGH A FIRST FLOOR VENT
 TO SHOW COMPLIANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 9.
 12. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; ALL SINKS.
 WASTE FOR SINKS SHALL RISE VERTICALLY TO A POINT ABOVE
 THE FLOOR BEFORE THE INDIVIDUAL FIXTURE DRAIN SHALL BE
 ALLOWED TO CONNECT TO IT TO INSURE COMPLIANCE WITH FBC
 PL 1002.1. THE FIXTURE DRAINS SHALL BE INDIVIDUALLY OR
 COMMON VENTED IN ACCORDANCE WITH FBC PL SECTIONS 910
 AND 911. COMMON VENTS SHALL BE SIZED IN ACCORDANCE WITH
 FBC PL TABLE 911.3.
 13. RE: PLAN SHEET P-2, WATER HEATER SCHEDULE; PER WPB
 FBC 107.2.1, REFER TO MANUFACTURER'S SPECIFICATION
 SHEET ON
 HTTPS://WWW.RHEEM.COM/PRODUCT/LIGHT-DUTY-ELD80-FTB.
 OPEN THE DOCUMENTS TAB AND FIND SPECIFICATION SHEET PDF
 AT BOTTOM OF DOCUMENTS. PROVIDE FULL ELECTRICAL
 CHARACTERISTICS OF THE WATER HEATER INCLUSIVE OF THE
 VOLTAGE (I.E. 240V), WATTAGE (I.E. 4500 WATTS
 NON-SIMULTANEOUS, SINGLE PHASE), STORAGE CAPACITY (I.E.
 80 GALLONS). RECONCILE ELECTRICAL CHARACTERISTICS WITH
 PLAN SHEET E-1 NEW PANEL A SCHEDULE.
 14. RE: PLAN SHEET P-2, WATER HEATER; PER WPB FBC
 107.2.1, PLEASE SHOW PAN DRAIN ROUTING AND POINT OF
 TERMINATION IN COMPLIANCE WITH FBC PL 504.7.2. THIS IS
 A SECOND REQUEST.
 15. RE: PLAN SHEET P-2, HOT WATER DISTRIBUTION; PER WPB
 FBC 107.2.1, PROVIDE TYPE, SIZE AND LOCATION OF THERMAL
 EXPANSION CONTROL DEVICE AS REQUIRED BY FBC PL 607.3
 16. RE: PLAN SHEET P-2, WATER RISER DIAGRAM AND PLAN
 VIEW; PER WPB FBC 107.2.1, PROVIDE SOURCE, SIZE AND
 LOCATION OF DOMESTIC WATER SERVICE/SUPPLY. PROVIDE
 PROTECTION OF WATER SUPPLE AS REQUIRED BY FBC PL
 SECTION 608
 17. RE: PLAN SHEET P-2, WATER RISER DIAGRAM AND PLAN
 VIEW; PER WPB FBC 107.2.1, PROVIDE AND SHOW WATER TO
 THE WATER CLOSETS AND THE SHOWERS. INCLUDE SIZING.
 18. RE: PLAN SHEET P-2, PLUMBING FIXTURE SCHEDULE/FLOW
 RATE REGARDING THE WATER HEATER; MANUFACTURER HAS
 PROVIDED 3/4 INCH WATER CONNECTIONS. AS SUCH IN KEEPING
 WITH MANUFACTURES RECOMMENDATIONS, WATER IN AND OUT
 SHALL BE SIZED 3/4 INCH.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19081206 1920 PALM BEACH LAKES BLVD # 214
  
  
  