Plan Review Notes
Plan Review Notes For Permit 19081206
Permit Number 19081206
Review Stop M
Sequence Number 2
Notes
Date Text
2019-11-18 13:34:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081206
 11/1819
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.THE COMMENTS LISTED BELOW
 FROM THE 1ST REVIEW STILL EXIST. PLEASE COMPLY.
  
 1) SHEET M-1: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW SYSTEM IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC, AND SECTION 312.1 FBC M.
 THE ARCHITECT'S NARRATIVE RESP0ONSE INDICATES BY
 OTHERS.
  
 2) M-1: REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-M. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
 ARCHITECT INDICATES BY OTHERS
  
 4) M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED FOR THE
 OCCUPANTS. IF AN O/A DUCT IS TO BE USED, PLEASE SHOW
 THE LOCATION OF THE DUCT, THE TYPE AND SIZE OF DUCT,
 AND THE LOCATION OF THE AIR INLET- SECTION 401.4 FBC M.
 NO CORRECTIONS TO THE PLANS WERE MADE
  
 5) M-1: IF AN O/A DUCT IS TO BE PROVIDED PLEASE PROVIDE
 AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER- SECTION
 C403.2.4.3 FBC- EC.
 NO CORRECTIONS TO THE PLANS WERE MADE.
  
 7) M-1: THE AC CLOSET AND DOORS SHALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION- SECTION C403.2.9.2 FBC
 EC, AND SECTION 602.1 FBC M.
 NO CORRECTIONS TO THE PLANS WERE MADE
  
 8) NEW COMMENT- M-1: THE 4" ROUND DUCT SUPPLYING 100
 CFMS OF AIR ARE UNDERSIZED PER TRANE DUCTULATER SIZING.
 PLEASE INCREASE THE DUCT SIZES TO 6" .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  