2019-11-19 10:03:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081206
 ADD: 1920 PALM BEACH LAKES SUITE: 214-215
 CONT: OCTAGON CONSTRUCTION GROUP INC.
 TEL: 561-676-4543
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 19/2019
 ACTION: DENIED
  
 1) COMPLETE.
  
 2) SHEET A-1:
 2A-B) COMPLIED.
  
 2C) IN EACH OF THE 2 ACCESSIBLE BATHROOMS THERE ARE
 NOTES FOR A HAND HELD SHOWER AND SHOWER DRAIN. PLEASE
 SHOW COMPLIANCE FOR AN ACCESSIBLE ROLL-IN SHOWER AND
 COMPLIANCE WITH 608.5.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 3A) COMPLIED, DUROCK TO CEILING.
  
 3B) 2ND REQUEST. NEW DETAIL DOES NOT GIVE ANY CEILING
 DETAIL. RESPONSE INDICATES S SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK IS ATTACHED.
 1ST ROUND COMMENT. SHEET A2 DETAIL 8 SHOWS THE USE OF
 AN ACOUSTICAL DROPPED CEILING FOR IN THE SHOWER
 COMPARTMENT. PLEASE REVIEW SECTION FBC-B 2509.3 WHERE
 WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED.
  
 3C) 2ND REQUEST. NO RESPONSE COMMENT TO THIS CODE
 ISSUE.
  
 3C)(1) THE PLANS ARE SILENT AS TO HOW THE JOINT FROM
 THE BACKER BOARD FOR TILE WILL BE SEALED TO THE FLOOR.
 THE 2017 FBC-B SECTION 1210.2.1 INDICATES THE
 INTERSECTIONS OF SUCH FLOORS WITH WALLS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT VERTICAL BASE THAT EXTENDS
 UPWARD ONTO THE WALLS NOT LESS THAN 4 INCHES.
  
 3C)(2) 2ND REQUEST. THE WHOLE ROOM NEEDS TO BE DESIGNED
 AS A SHOWER. PLEASE PROVIDE A BLOWN UP DETAIL FOR
 COMPLIANCE WITH THE SHOWER PLAN INTERSECTS WITH THE
 WALL AND TO WHAT HEIGHT THE SHOWER PAN NEEDS TO BE IN
 THE VERTICAL PLANE AND THE LAP OF THE DUROROCK BOARD.
 1ST ROUND OF COMMENTS. NOR HOW THE FLOOR WILL BE
 SEALED, PITCHED TO THE DRAIN NOR THE REQUIREMENTS UNDER
 THE PLUMBING CODE FOR A SHOWER LINING. FBC-P 417.2. /
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) SEMI-COMPLIED. SHEET A-2 DETAIL # 4 NOW SHOWS THE
 MIRROR WITH A TRIM SURROUND. THE VERTICAL MEASUREMENT
 IS TAKEN FROM FINISH FLOOR TO THE BOTTOM EDGE OF THE
 MIRROR, NOT THE BOTTOM OF THE
 REFLECTIVE SURFACE.
 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3E) NEW COMMENT. SHEET A-2 DETAIL 3 IS A CODE COMPLIANT
 FOR THE WATER CLOSET PAPER DISPENSER. THE ISSUE
 IS WITH DETAIL # 7 AND THE UPPER LEFT NOMENCLATURE (A)
 FOR THE WATER CLOSET PAPER DISPENSER ARE NOT IN THE
 CORRECT LOCATION.
 TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 3F) NEW COMMENT. SHEET A2 DETAILS 2 & 3 BOTH SHOW THE
 GRAB BAR BEING MEASURED FROM FINISH FLOOR TO THE CENTER
 OF THE GRAB BAR. PLEASE SHOW COMPLIANCE WITH:
 GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1ST ROUND OF COMMENTS. IN THE OLD LAYOUT OF THE
 RESTROOMS THERE WERE NO WINDOWS ON THE EXTERIOR WALL.
 ON THE NEW LAYOUT THE ADA RESTROOM # 2 HAS THE LAVATORY
 IN THE WINDOW. THE PLANS DO NOT HAVE A DETAIL FOR THIS
 CONFIGURATION, THE SUBMITTED ADA DETAIL 4 ON SHEET A-2
 HAS A MIRROR LOCATED BEHIND THE LAV. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED, CODE COMPLIANCE
 CANNOT BE DETERMINED AT THIS TIME.
  
 4) 2ND REQUEST. THIS IS A CONDO BUILDING. WITH THE
 UNIFYING 2 UNITS YOU NEED TO COMPLETE A UNITY OF TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  