| Date |
Text |
| 2019-11-19 10:03:41 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19081206 |
| | ADD: 1920 PALM BEACH LAKES SUITE: 214-215 |
| | CONT: OCTAGON CONSTRUCTION GROUP INC. |
| | TEL: 561-676-4543 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. NOV. 19/2019 |
| | ACTION: DENIED |
| | |
| | 1) COMPLETE. |
| | |
| | 2) SHEET A-1: |
| | 2A-B) COMPLIED. |
| | |
| | 2C) IN EACH OF THE 2 ACCESSIBLE BATHROOMS THERE ARE |
| | NOTES FOR A HAND HELD SHOWER AND SHOWER DRAIN. PLEASE |
| | SHOW COMPLIANCE FOR AN ACCESSIBLE ROLL-IN SHOWER AND |
| | COMPLIANCE WITH 608.5.2 STANDARD ROLL-IN TYPE SHOWER |
| | COMPARTMENTS. |
| | IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE |
| | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| | INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT |
| | IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY |
| | UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO |
| | THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM) |
| | MAXIMUM FROM THE SEAT WALL. |
| | |
| | 3A) COMPLIED, DUROCK TO CEILING. |
| | |
| | 3B) 2ND REQUEST. NEW DETAIL DOES NOT GIVE ANY CEILING |
| | DETAIL. RESPONSE INDICATES S SIGNED CONTRACT WITH SCOPE |
| | AND VALUE OF WORK IS ATTACHED. |
| | 1ST ROUND COMMENT. SHEET A2 DETAIL 8 SHOWS THE USE OF |
| | AN ACOUSTICAL DROPPED CEILING FOR IN THE SHOWER |
| | COMPARTMENT. PLEASE REVIEW SECTION FBC-B 2509.3 WHERE |
| | WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED. |
| | |
| | 3C) 2ND REQUEST. NO RESPONSE COMMENT TO THIS CODE |
| | ISSUE. |
| | |
| | 3C)(1) THE PLANS ARE SILENT AS TO HOW THE JOINT FROM |
| | THE BACKER BOARD FOR TILE WILL BE SEALED TO THE FLOOR. |
| | THE 2017 FBC-B SECTION 1210.2.1 INDICATES THE |
| | INTERSECTIONS OF SUCH FLOORS WITH WALLS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT VERTICAL BASE THAT EXTENDS |
| | UPWARD ONTO THE WALLS NOT LESS THAN 4 INCHES. |
| | |
| | 3C)(2) 2ND REQUEST. THE WHOLE ROOM NEEDS TO BE DESIGNED |
| | AS A SHOWER. PLEASE PROVIDE A BLOWN UP DETAIL FOR |
| | COMPLIANCE WITH THE SHOWER PLAN INTERSECTS WITH THE |
| | WALL AND TO WHAT HEIGHT THE SHOWER PAN NEEDS TO BE IN |
| | THE VERTICAL PLANE AND THE LAP OF THE DUROROCK BOARD. |
| | 1ST ROUND OF COMMENTS. NOR HOW THE FLOOR WILL BE |
| | SEALED, PITCHED TO THE DRAIN NOR THE REQUIREMENTS UNDER |
| | THE PLUMBING CODE FOR A SHOWER LINING. FBC-P 417.2. / |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3D) SEMI-COMPLIED. SHEET A-2 DETAIL # 4 NOW SHOWS THE |
| | MIRROR WITH A TRIM SURROUND. THE VERTICAL MEASUREMENT |
| | IS TAKEN FROM FINISH FLOOR TO THE BOTTOM EDGE OF THE |
| | MIRROR, NOT THE BOTTOM OF THE |
| | REFLECTIVE SURFACE. |
| | 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. MIRRORS |
| | LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 3E) NEW COMMENT. SHEET A-2 DETAIL 3 IS A CODE COMPLIANT |
| | FOR THE WATER CLOSET PAPER DISPENSER. THE ISSUE |
| | IS WITH DETAIL # 7 AND THE UPPER LEFT NOMENCLATURE (A) |
| | FOR THE WATER CLOSET PAPER DISPENSER ARE NOT IN THE |
| | CORRECT LOCATION. |
| | TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 |
| | DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH |
| | 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| | BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE |
| | THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW |
| | CONTINUOUS PAPER FLOW. |
| | |
| | 3F) NEW COMMENT. SHEET A2 DETAILS 2 & 3 BOTH SHOW THE |
| | GRAB BAR BEING MEASURED FROM FINISH FLOOR TO THE CENTER |
| | OF THE GRAB BAR. PLEASE SHOW COMPLIANCE WITH: |
| | GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 1ST ROUND OF COMMENTS. IN THE OLD LAYOUT OF THE |
| | RESTROOMS THERE WERE NO WINDOWS ON THE EXTERIOR WALL. |
| | ON THE NEW LAYOUT THE ADA RESTROOM # 2 HAS THE LAVATORY |
| | IN THE WINDOW. THE PLANS DO NOT HAVE A DETAIL FOR THIS |
| | CONFIGURATION, THE SUBMITTED ADA DETAIL 4 ON SHEET A-2 |
| | HAS A MIRROR LOCATED BEHIND THE LAV. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED, CODE COMPLIANCE |
| | CANNOT BE DETERMINED AT THIS TIME. |
| | |
| | 4) 2ND REQUEST. THIS IS A CONDO BUILDING. WITH THE |
| | UNIFYING 2 UNITS YOU NEED TO COMPLETE A UNITY OF TITLE. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |