| 2019-09-16 12:22:12 | 1ST REVIEW: 19081206 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT A-1 THERE ARE NOTES IN THE BATHROOM REFERRING TO |
| | A SHOWER NONE IS SHOWN ON THE PLAN PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE INSIDE WIDTH OF THE BATHROOMS NEEDS TO BE A MIN |
| | OF 7'1" TO PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR |
| | ACCESSIBILITY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3.SHOW DIMENSIONS ON THE CLEAR FLOOR FOR THE LAVATORY |
| | AND TOILET. PER FBC ACC 604.3.1 SIZE. CLEARANCE AROUND |
| | A WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM |
| | MEASURED PERPENDICULAR FROM THE REAR WALL. |
| | 606.2-305.3 SIZE. THE CLEAR FLOOR OR GROUND SPACE SHALL |
| | BE 30 INCHES MINIMUM BY 48 INCHES MINIMUM. |
| | |
| | 4.THE BREAK ROOM SINK, INFUSION SINK AND AT LEAST ONE |
| | OF THE EXAM ROOM SINK SHALL COMPLY WITH ACCESSIBILITY. |
| | PER FBC ACC 212.2, 212.3, 606.2, 606.3 |
| | |
| | 5. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4 |
| | |
| | 6. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND.PER FBC ACC 603.3 |
| | |
| | 7. SHT. A-2 DETAIL #4 THE DRAWING ON THE RIGHT OF THE |
| | LAVATORY HAS A DIMENSION OF 3'4" TO THE LIP OF THE |
| | LAVATORY IT SHALL BE A MAXIMUM OF 34". PER FBC ACC |
| | 606.3 |
| | |
| | 8.SHT. P-1 SANITARY THERE SHALL BE AT LEAST ONE VENT |
| | SHALL EXTEND THROUGH ROOF. PER FBC PL 904.1 |
| | |
| | 9. SHT. P-1 THE SANITARY ISOMETRIC SHOWS A SHOWER THE |
| | FLOOR PLAN IS MISSING A SHOWER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 10. THE BREAK ROOM SINK SHALL CONNECT TO THE BUILDING |
| | DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL |
| | 912.1 |
| | |
| | 11. SHT P-1 ON THE THE SANITARY ISOMETRIC THE VENTS |
| | SHALL BE SHOWN ON THE LAVATORY STACKS. PER FBC PL |
| | 901.2.1 |
| | |
| | 12. SHT P-2 SHUT OFF VALVES ARE ON ALL DOWN FED WATER |
| | PIPING SHOWN ON THE WATER ISOMETRIC. PER FBC PL |
| | 606.1(5) |
| | |
| | 13.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC PL |
| | 504.7.2,607.3 |
| | |
| | 14.LIST MANUFACTURE SIZE AND MODEL OF THE WATER HEATER. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 15. PLEASE SIZE THE PIPING ON THW WATER ISOMETRIC. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 16. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |