Plan Review Notes
Plan Review Notes For Permit 19081206
Permit Number 19081206
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-16 12:22:121ST REVIEW: 19081206
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A-1 THERE ARE NOTES IN THE BATHROOM REFERRING TO
 A SHOWER NONE IS SHOWN ON THE PLAN PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. THE INSIDE WIDTH OF THE BATHROOMS NEEDS TO BE A MIN
 OF 7'1" TO PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR
 ACCESSIBILITY. PER WPB AMEND TO FBC 107.2.1
  
 3.SHOW DIMENSIONS ON THE CLEAR FLOOR FOR THE LAVATORY
 AND TOILET. PER FBC ACC 604.3.1 SIZE. CLEARANCE AROUND
 A WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL.
 606.2-305.3 SIZE. THE CLEAR FLOOR OR GROUND SPACE SHALL
 BE 30 INCHES MINIMUM BY 48 INCHES MINIMUM.
  
 4.THE BREAK ROOM SINK, INFUSION SINK AND AT LEAST ONE
 OF THE EXAM ROOM SINK SHALL COMPLY WITH ACCESSIBILITY.
 PER FBC ACC 212.2, 212.3, 606.2, 606.3
  
 5. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 6. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.PER FBC ACC 603.3
  
 7. SHT. A-2 DETAIL #4 THE DRAWING ON THE RIGHT OF THE
 LAVATORY HAS A DIMENSION OF 3'4" TO THE LIP OF THE
 LAVATORY IT SHALL BE A MAXIMUM OF 34". PER FBC ACC
 606.3
  
 8.SHT. P-1 SANITARY THERE SHALL BE AT LEAST ONE VENT
 SHALL EXTEND THROUGH ROOF. PER FBC PL 904.1
  
 9. SHT. P-1 THE SANITARY ISOMETRIC SHOWS A SHOWER THE
 FLOOR PLAN IS MISSING A SHOWER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 10. THE BREAK ROOM SINK SHALL CONNECT TO THE BUILDING
 DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL
 912.1
  
 11. SHT P-1 ON THE THE SANITARY ISOMETRIC THE VENTS
 SHALL BE SHOWN ON THE LAVATORY STACKS. PER FBC PL
 901.2.1
  
 12. SHT P-2 SHUT OFF VALVES ARE ON ALL DOWN FED WATER
 PIPING SHOWN ON THE WATER ISOMETRIC. PER FBC PL
 606.1(5)
  
 13.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC PL
 504.7.2,607.3
  
 14.LIST MANUFACTURE SIZE AND MODEL OF THE WATER HEATER.
 PER WPB AMEND TO FBC 107.2.1
  
 15. PLEASE SIZE THE PIPING ON THW WATER ISOMETRIC. PER
 WPB AMEND TO FBC 107.2.1
  
 16. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]