Plan Review Notes
Plan Review Notes For Permit 19081206
Permit Number 19081206
Review Stop M
Sequence Number 1
Notes
Date Text
2019-09-17 08:16:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081206
 9/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW SYSTEM IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC, AND SECTION 312.1 FBC M.
  
 2) M-1: REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-M. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 3) M-1: THE CORRIDOR SHALL NOT BE USED TO CONVEY RETURN
 AIR FROM THE ROOMS TO THE AIR HANDLER- SECTION 601.2
 FBC M. DUCTED RETRUNS FROM THE ROOMS ARE REQUIRED.
  
 4) M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED FOR THE
 OCCUPANTS. IF AN O/A DUCT IS TO BE USED, PLEASE SHOW
 THE LOCATION OF THE DUCT, THE TYPE AND SIZE OF DUCT,
 AND THE LOCATION OF THE AIR INLET- SECTION 401.4 FBC M.
  
 5) M-1: IF AN O/A DUCT IS TO BE PROVIDED PLEASE PROVIDE
 AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER- SECTION
 C403.2.4.3 FBC- EC.
  
 6) M-1: THERE IS A NOTE INDICATING A DUCT SMOKE
 DETECTOR WILL BE INSTALLED IN THE RETRUN AIR SYSTEM OF
 THE NEW AIR HANDLER. PLEASE NOTE THAT DUCT SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY AIR SYSTEMS OF AIR
 HANDLERS WITH THE CAPACITIES EXCEEDING 2000 CFMS-
 SECTION 606.2.1 FBC M.
  
 7) M-1: THE AC CLOSET AND DOORS SHALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION- SECTION C403.2.9.2 FBC
 EC, AND SECTION 602.1 FBC M.
  
 8) M-1: MECHANICAL EXHAUST VENTILATION REQUIRED FOR THE
 TOILET ROOMS- SECTION 1203.5.2.1 FBC B AND TABLE
 403.3.1.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  