Plan Review Notes
Plan Review Notes For Permit 19081206
Permit Number 19081206
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-17 10:57:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081206
 ADD: 1920 PALM BEACH LAKES SUITE: 214-215
 CONT: OCTAGON CONSTRUCTION GROUP INC.
 TEL: 561-676-4543
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 17/2019
 ACTION: DENIED
  
 1) THE COVERSHEET:
 1A) CODE RESEARCH INDICATES THE MINIMUM BUILDING TYPE
 AS TYPE III. THERE IS A QUESTION AS TO WHICH CODE YOU
 ARE REFERENCING. THIS BUILDING WAS BUILT IN 1976, ARE
 YOU REFERENCING THE CODE AT TIME THE BUILDING WAS
 BUILT? THE CONSTRUCTION TYPE ALSO CHANGED FROM THE 2001
 FBC-B TYPE III CONSTRUCTION TO IN THE 2004 FBC TO IV
 HEAVY TIMBER. TODAYS CODE THE 2017 FBC-B THE
 TERMINOLOGY WOULD BE:
 TYPE III-A 1-HOUR PROTECTED
 TYPE III-B NON-PROTECTED
 PLEASE INDICATE THE CURRENT CONSTRUCTION TYPE.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE COVERSHEET UNDER THE HEADING CODE RESEARCH,
 LIST FIRE WALLS EXISTING 2- HOUR TENANT SEPARATION
 WALLS. THE TERM FIRE WALLS IS A TERM USED TO SEPARATE A
 BUILDING INTO SEPARATE FIRE AREAS IN ORDER TO NOT FIRE
 SPRINKLER A BUILDING, SEE FBC-B 706.1. FIRE BARRIER
 WALLS SEPARATE OCCUPANCIES, SHAFT, INTERIOR EXIT
 STAIRWAYS EXIT ENCLOSURES, EXIT PASSAGEWAYS AND ATRIUMS
 SEE FBC-B 707.1. FIRE PARTITIONS SEPARATE TENANT SPACES
 THAT ARE THE SAME OCCUPANCY TYPE SEE FBC-B 708.1.
 PLEASE CORRECT TERMINOLOGY.
  
 1C) THE COVERSHEET UNDER THE HEADING CODE RESEARCH,
 LIST FIRE WALLS EXISTING 2- HOUR TENANT SEPARATION
 WALLS (FIRE PARTITION) WHEREAS SHEET D-1 & A-1 BOTH
 INDICATE THE SAME TENANT SEPARATION WALL(DEMISING WALL)
 AS A ONE HOUR WALL. PLEASE UPDATE THE PLANS TO SHOW
 CONSISTENCY. 107.2.1.2.
  
 2) SHEET A-1:
 2A) SHEET A-1 INDICATES CHAIRS NEXT TO THE INSWING
 DOORWAY IN THE WAITING ROOM AND THE INFUSION ROOM.
 TO SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 404.2.4, TABLE 404.2.4.1 & FIGURE 404.2.4.1(A).
  
 2B) THE DEMO PLAN SHOWS ALL OF THE WALLS OF THE
 EXISTING BATHROOMS REMOVED. THE PROPOSED FLOOR PLAN
 INDICATES A BACKWALL MEASUREMENT OF 6 FEET 9 INCHES.
 THIS MEASUREMENT IS TOO SMALL TO SHOW COMPLIANCE WITH
 THE ACCESS. CODE SECTION 604.3.1 SIZE AND 604.3.2
 OVERLAP. THE MINIMUM MEASUREMENT FINISH TO FINISH IS 7
 FEET 1 INCH.
  
 2C) IN EACH OF THE 2 ACCESSIBLE BATHROOMS THERE ARE
 NOTES FOR A HAND HELD SHOWER AND SHOWER DRAIN. PLEASE
 SHOW COMPLIANCE FOR AN ACCESSIBLE ROLL-IN SHOWER AND
 COMPLIANCE WITH 608.5.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.
  
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 3A) SHEET A2 DETAIL 8 HAS NOTES DEALING WITH THE SHOWER
 WALLS IN THE ACCESSIBLE RESTROOMS. THE NOTE INDICATES
 THE USE OF DUROCK UP 4 FEET AND MR BOARD ABOVE. ALL
 WALLS TO BE CERAMIC TILE FULL HEIGHT.
 PLEASE REVIEW THE 2017 FBC-B SECTION 2509.2 ACCEPTABLE
 MATERIALS TO BE USED FOR TILE BASE IN SHOWERS.
  
 3B) SHEET A2 DETAIL 8 SHOWS THE USE OF AN ACOUSTICAL
 DROPPED CEILING FOR IN THE SHOWER COMPARTMENT. PLEASE
 REVIEW SECTION FBC-B 2509.3 WHERE WATER RESISTANT
 GYPSUM BACKING BOARD SHALL NOT BE USED.
 (1) OVER A VAPOR RETARDER IN A SHOWER COMPARTMENT.
  
 3E) THE PLANS ARE SILENT AS TO HOW THE JOINT FROM THE
 BACKER BOARD FOR TILE WILL BE SEALED TO THE FLOOR NOR
 HOW THE FLOOR WILL BE SEALED, PITCHED TO THE DRAIN NOR
 THE REQUIREMENTS UNDER THE PLUMBING CODE FOR A SHOWER
 LINING. FBC-P 417.2. / 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3C) IN THE OLD LAYOUT OF THE RESTROOMS THERE WERE NO
 WINDOWS ON THE EXTERIOR WALL. ON THE NEW LAYOUT THE ADA
 RESTROOM # 2 HAS THE LAVATORY IN THE WINDOW. THE PLANS
 DO NOT HAVE A DETAIL FOR THIS CONFIGURATION, THE
 SUBMITTED ADA DETAIL 4 ON SHEET A-2 HAS A MIRROR
 LOCATED BEHIND THE LAV. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, CODE COMPLIANCE CANNOT BE
 DETERMINED AT THIS TIME.
  
 4) THIS IS A CONDO BUILDING. WITH THE UNIFYING 2 UNITS
 YOU NEED TO COMPLETE A UNITY OF TITLE.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  