| 2020-06-23 14:03:09 | 1) SHT. A0.0 NOTES THE OCCUPANT LOAD AS 38 PERSONS AND |
| | SHT.A2.0 NOTES THE OCCUPANT LOAD AS 19 PERSONS. |
| | CLARIFY. |
| | 2) IF THE OCCUPANT LOAD EXCEEDS 15 PERSONS, SEPARATE |
| | TOILET FACILITIES ARE REQUIRED FOR MALES AND FEMALES IN |
| | ACCORDANCE WITH FBC-PLUMBING SEC.403.2 AND TABLE 403.1. |
| | SINCE THIS IS CLASSIFIED AS A BUSINESS OCCUPANCY, THERE |
| | SHALL BE ONE WATER CLOSET AND LAVATORY FOR THE FIRST 25 |
| | MALES AND ONE WATER CLOSET AND LAVATORY FOR THE FIRST |
| | 40 FEMALES PER FBC-PLUMBING TABLE 403.1. |
| | 3) DUE TO THE OCCUPANT LOAD THE PLUMBING CODE REQUIRES |
| | A DRINKING FOUNTAIN PER TABLE 403.1. THE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH FBC-ACCESS. SEC. 211 AND |
| | FBC-PLUMBING SEC.410.3. |
| | 4) SHT. A2.1 - DETAIL #1 - THE GRAB BAR ADJACENT TO THE |
| | WATER CLOSET IS SHOWN AS 36 INCHES IN LENGTH. THE |
| | MINIMUM LENGTH SHALL BE 42 INCHES IN ACCORDANCE WITH |
| | FBC-ACCESS. SEC. 604.5.1. |
| | 5) SHT. P1.1 - THE PLUMBING PLAN STILL SHOWS A SHOWER |
| | ON THE EXTERIOR WHICH WAS SUPPOSED TO BE DELETED. |
| | CLARIFY. |
| | 6) SHT. P1.1 - BACKFLOW PREVENTION SCHEDULE - THE |
| | BACKFLOW DEVICE FOR THE ICE MACHINE IS FOR CARBONATION |
| | AND BEVERAGE DISPENSING MACHINES AND SHALL COMPLY WITH |
| | ASSE 1024 PER FBC-PLUMBING SEC.608.13.10. THIS UNIT |
| | DOES NOT. |
| | 7) SHT. P1.1 - PLACE A NOTE ON THE PLANS THAT ALL THE |
| | BACKFLOW PREVENTION DEVICES WILL BE LEAD FREE. 2ND |
| | REQUEST |
| | 8) SUBMIT A DETAIL SHOWING THE CONNECTION OF THE HOT |
| | WATER RETURN LINE TO THE WATER HEATER COLD WATER LINE. |
| | WPB AMEND. TO FBC SEC. 107.2.1. SHT. P1.1 DOES NOT SHOW |
| | THIS CONNECTION. 2ND REQUEST. |
| | 9) A BACKFLOW PREVENTION DEVICE MUST BE INSTALLED AT |
| | THE WATER METER ON THE WATER SERVICE TO THIS STRUCTURE |
| | PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION |
| | CONTROL MANUAL.THE DEVICE MUST BE A REDUCED PRESSURE |
| | ZONE DEVICE AND MUST BE LEAD FREE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |