| 2019-11-08 10:45:34 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19081141 |
| | 11/8/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2.1: I WAS UNABLE TO LOCATE A PERMIT FOR THE |
| | NEW 5-TON SYSTEM PER THE NOTE ON THE PLAN SHEET THAT |
| | INDICATES IT WAS DONE UNDER A SEPARATE PERMIT. I |
| | CHECKED THE ADDRESSES ON THE PLANS AND ON THE PERMIT |
| | APPLICATION AND UNDER THE APPLICATION ADDRESS OF 7391 |
| | RIVERWALK CIR THERE WAS A 2.5 TON AC CHANGEOUT PERMIT |
| | ISSUED ON 12/04/2018 (PERMIT #18120044). |
| | PLEASE NOTE THE PLANS ARE INDICATING AN INCORRECT |
| | PROJECT ADDRESS- 7459 RIVERWALK CIR.- PLEASE CORRECT. |
| | |
| | 2) SHEET 2.1: 2ND REQUEST FOR AN AC EQUIPMENT SCHEDULE |
| | AND VENTILATION CALCULATIONS ON THE PLAN, AND AC |
| | COOLING AND HEATING CALCULATIONS TO BE SUBMITTED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |