2019-09-17 12:21:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081141
 9/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2.1: PROVIDE AN AC EQUIPMENT SCHEDULE ON THE
 PLAN- SECTION 107.1 WPB
  
 2) 2.1: THE OUTSIDE AIR CALCULATIONS ARE INDICATING
 1046 CFMS OF O/A PROVIDED BY AN RTU, HOWEVER A 4-TON
 SPLIT SYSTEM IS SHOWN ON THE PLAN. PLEASE NOTE THAT A
 4-TON SYSTEM WILL GENERALLY PROVIDE 1600 CFMS OF AIR
 AND CAN TYPICALLY CONDTION AND DEHUMIDIFY APPROXIMATELY
 15-25% OF THAT VOLUME IN OUTSIDE AIR, OR IN THIS CASE,
 APPROXIMATELY 400 CFMS MAX. IN ORDER TO PROVIDE 1046
 CFMS OF O/A A LARGER CAPACITY SYSTEM IS REQUIRED.
  
 3) 2.1: PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 THE NEW SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC
 EC, AND SECTION 312.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  