| Date |
Text |
| 2019-09-17 12:21:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19081141 |
| | 9/17/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2.1: PROVIDE AN AC EQUIPMENT SCHEDULE ON THE |
| | PLAN- SECTION 107.1 WPB |
| | |
| | 2) 2.1: THE OUTSIDE AIR CALCULATIONS ARE INDICATING |
| | 1046 CFMS OF O/A PROVIDED BY AN RTU, HOWEVER A 4-TON |
| | SPLIT SYSTEM IS SHOWN ON THE PLAN. PLEASE NOTE THAT A |
| | 4-TON SYSTEM WILL GENERALLY PROVIDE 1600 CFMS OF AIR |
| | AND CAN TYPICALLY CONDTION AND DEHUMIDIFY APPROXIMATELY |
| | 15-25% OF THAT VOLUME IN OUTSIDE AIR, OR IN THIS CASE, |
| | APPROXIMATELY 400 CFMS MAX. IN ORDER TO PROVIDE 1046 |
| | CFMS OF O/A A LARGER CAPACITY SYSTEM IS REQUIRED. |
| | |
| | 3) 2.1: PROVIDE AC COOLING AND HEATING CALCULATIONS FOR |
| | THE NEW SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC |
| | EC, AND SECTION 312.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |