| 2019-09-16 14:41:06 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19081141 |
| | ADD: 7391 RIVERWALK CIR. |
| | CONT: PALM BEACH COUNTY CONTRACTOR CORP. |
| | TEL: 561-257-3706 [email protected] |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 16/2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1.1. SHEET 1.1 DOES NOT SHOW ANY DRINKING |
| | FOUNTAINS. PLEASE SHOW COMPLIANCE WITH 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 211.2MINIMUM NUMBER. NO |
| | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 2) THIS SHEET 1.1. THERE IS NO DIMENSIONS NOR DETAILS |
| | FOR THE RESTROOMS. MISSING ENLARGED FLOOR PLAN DETAIL |
| | SHOWING COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE |
| | SECTIONS: |
| | |
| | 2A) 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL |
| | BE 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR |
| | FROM THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM |
| | MEASURED PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 2B) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE |
| | WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER |
| | CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY |
| | NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE |
| | ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT |
| | OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER |
| | FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE |
| | REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | |
| | 2C) 606 LAVATORIES AND SINKS. 2017 FBC-ACCESSIBILITY |
| | CODE 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 2D) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2E) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| | FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| | METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| | MINIMUM. |
| | |
| | 2F) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | |
| | |
| | 2G) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 2H) GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 2I) TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE |
| | 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY |
| | WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| | BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE |
| | THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW |
| | CONTINUOUS PAPER FLOW. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |