Plan Review Notes
Plan Review Notes For Permit 19081130
Permit Number 19081130
Review Stop P
Sequence Number 2
Notes
Date Text
2019-10-01 11:46:52PROVISO APPROVAL, REVIEWED BY TIM HUNT
  
 1) WATER HEATER RELIEF SHALL DISCHARGE THOUGH AN AIR
 CAP IN THE SAME ROOM AS THE HEATER AND NOT CONNECT INTO
 THE DRAINAGE SYSTEM FBC-PLB 504.6
  
  
 2) A WATER HEATER PAN AND PAN DRAIN IS REQUIRED. PAN
 DRAIN SHALL BE DRAINED BY AN INDIRECT WASTE PIPE TO AN
 APPROVED WASTE RECEPTOR, FLOOR DRAIN, OR DISCHARGE TO
 THE OUTSIDE. FBC-PLB 504.7, 504.7.1, 504.7.2
  