| Plan Review Notes For Permit 19081130 |
| Permit Number |
19081130 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-09 07:50:59 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) SHOW KITCHENETTE CLEAR FLOOR SPACE ON PLAN 30? X | | | 48?. A FORWARD APPROACH IS REQUIRED. FBC-ACC 804.3.1 | | | 2) PROVIDE CLEAR FLOOR SPACE ON PLAN FOR ALL KITCHEN | | | APPLIANCES. FBC-ACC 804.6.1, 804.6.4 | | | 3) PASS THROUGH KITCHENETTES REQUIRE 40? MIN BETWEEN | | | ALL WALLS, CABINETS AND FIXTURES. YOUR PLAN SHOWS ONLY | | | 36?. FBC-ACC 804.2.1 | | | 4) THE TANKLESS WATER HEATER SPEC PROVIDE IS NOT ABLE | | | TO PRODUCE HOT WATER TO THIS FIXTURE AS REQUIRED. | | | FBC-PLB 607.1. HEAT RISE MUST BE MIN 40F @ 2.2 GPM. | | | FBC-PLB 604.3 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|