2019-09-09 07:50:59PLUMBING 1ST REVIEW**DENIED**
  
 1) SHOW KITCHENETTE CLEAR FLOOR SPACE ON PLAN 30? X
 48?. A FORWARD APPROACH IS REQUIRED. FBC-ACC 804.3.1
 2) PROVIDE CLEAR FLOOR SPACE ON PLAN FOR ALL KITCHEN
 APPLIANCES. FBC-ACC 804.6.1, 804.6.4
 3) PASS THROUGH KITCHENETTES REQUIRE 40? MIN BETWEEN
 ALL WALLS, CABINETS AND FIXTURES. YOUR PLAN SHOWS ONLY
 36?. FBC-ACC 804.2.1
 4) THE TANKLESS WATER HEATER SPEC PROVIDE IS NOT ABLE
 TO PRODUCE HOT WATER TO THIS FIXTURE AS REQUIRED.
 FBC-PLB 607.1. HEAT RISE MUST BE MIN 40F @ 2.2 GPM.
 FBC-PLB 604.3
  