Plan Review Notes
Plan Review Notes For Permit 19081130
Permit Number 19081130
Review Stop M
Sequence Number 1
Notes
Date Text
2019-09-16 09:18:331ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081130
 9/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 1) SHEET M102: THE LOUVERED AC DOORS SHALL BE NON
 COMBUSTIBLE PER SECTION C403.2.9.2 FBC EC. WOOD DOORS
 ARE SPECIFIED IN THE SCHEDULE ON SHEET A6.00.
  
 2) M102: REVISE NOTES #6, 7, 8 TO REMOVE MANUAL
 DAMPERS- C403.2.4.3 FBC EC.
  
 3) M102: PROVIDE A NOTE INDICATING A TEST AND BALANCE
 REPORT FOR THE NEW AC SYSTEMS WILL BE PROVIDED FOR
 FINAL APPROVAL- SECTION C408.2.2 FBC EC.
  
 4) PROVIDE AC LOAD CALCULATIONS FOR THE PROPOSED NEW
 SYSTEMS- SECTION C403.2.1 FBC EC, SECTION 312.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  