| 2019-09-16 09:18:33 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19081130 |
| | 9/16/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 1) SHEET M102: THE LOUVERED AC DOORS SHALL BE NON |
| | COMBUSTIBLE PER SECTION C403.2.9.2 FBC EC. WOOD DOORS |
| | ARE SPECIFIED IN THE SCHEDULE ON SHEET A6.00. |
| | |
| | 2) M102: REVISE NOTES #6, 7, 8 TO REMOVE MANUAL |
| | DAMPERS- C403.2.4.3 FBC EC. |
| | |
| | 3) M102: PROVIDE A NOTE INDICATING A TEST AND BALANCE |
| | REPORT FOR THE NEW AC SYSTEMS WILL BE PROVIDED FOR |
| | FINAL APPROVAL- SECTION C408.2.2 FBC EC. |
| | |
| | 4) PROVIDE AC LOAD CALCULATIONS FOR THE PROPOSED NEW |
| | SYSTEMS- SECTION C403.2.1 FBC EC, SECTION 312.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |