| Plan Review Notes For Permit 19081109 |
| Permit Number |
19081109 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-22 13:21:13 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PROVISIO | | | | | | 1) PANEL NEEDS MAIN | | | 2) NEED SIZE OF WATER HEATER | | | 3) SEE APNEL SCHEDULE FOR PROBLEMS | | | 4) NEED BRANCH CKT #S ON PLAN | | | 5) NEED LOAD CALC FOR SERVICE | | | 6) NEED FAULT CURRENT CALC FOR SERVICE | | | 7) PLAN SHOWS 4 SWITCHES IN DOORWAY | | | 8) E5 NOT SHOWN ON PANEL SCHEDULE | | | | | | SUBMIT BEFORE FINAL ELECTRICAL INSPECTION. |
|