| 2019-08-22 16:04:49 | 08/22/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS. |
| | |
| | NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE |
| | ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE |
| | SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED |
| | ON THE RESUBMITTAL REVIEW. |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED, SUBMIT AN ISOMETRIC |
| | DRAWING THAT CLEARLY SHOWS, UNIONS, SHUTOFF VALVES ON |
| | SYSTEM, REGULATOR AND THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER THE 2017 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 2. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC RES. SEC. G2413.3 |
| | |
| | 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. TYPE OF GAS LABELED ON PLANS PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC FG |
| | RES. SEC. G2413.2. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR POOL HEATER EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FG RES. SEC. G2408.1. |
| | THE POOL HEATER SHALL HAVE A MINIMUM THERMAL EFFICIENCY |
| | OF 82% PER THE 2017 FBC-ENERGY SEC. R403.10.4. |
| | |
| | 8. IN 2013 THERE WHERE GAS APPLIANCES INSTALLED, AND |
| | THE BTU?S ARE DIFFERENT FROM THE ONES SUBMITTED. THE |
| | GAS TANKLESS IS 180 BTU?S AN THE NEW ONE IS 160 BTU?S |
| | PLEASE CLARIFY PER THE 2017 FBC RES. SEC. G2413. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | |