| Date |
Text |
| 2019-10-17 17:15:26 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | FBC M = FBC MECHANICAL |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | FBC B 107.2.1: |
| | 1. PROVIDE A SURVEY/LAYOUT SHEET INDICATING THE |
| | LOCATION OF PROPOSED STAIR LOCATION. |
| | |
| | 2. PROVIDE DETAILS ON ALL PARTS OF STAIRS INCLUDING: |
| | (LANDING & STEP GRATING SURFACE?/SIZE OF OPEN SPACES IN |
| | GRATING?), (FOOTING DETAILS? EXISTING OR NEW?). |
| | |
| | 3. PROVIDE CONNECTION DETAILS INCLUDING: (FOR BOLTING |
| | PROVIDE TYPE/SIZE AND SPACING OF BOLTS) AND/OR (FOR |
| | WELDING PROVIDE THE WELDING PROCEDURE AND GENERAL |
| | DETAILS FOR REVIEW). |
| | |
| | AFTER REVIEW HAS BEEN APPROVED, AS PER AWS D1.1 CLAUSE |
| | 3.1: AT TIME OF INSPECTION PLEASE PROVIDE A WELD |
| | PROCEDURE SPECIFICATION; THE W.P.S. SPECIFIES THE |
| | REQUIRED ESSENTIAL VARIABLES INCLUDING: BASE MATERIALS, |
| | JOINTS, PROCESS, AND FILLER METALS TO BE USED. |
| | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |