| 2023-05-23 14:58:34 | INSUFFICIENT |
| | |
| | HOTWIRE P446 N. TERRACE & 41ST STREET |
| | |
| | REPEAT COMMENT: IN ACCORDANCE WITH SECTIONS 78-402(B) |
| | AND 78-411(B)(4) OF THE CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, THE CITY OF WEST PALM BEACH IS REQUESTING |
| | THAT THIS PROPOSED SMALL WIRELESS FACILITY BE MOVED TO |
| | ANOTHER LOCATION IN THE RIGHT-OF-WAY AND PLACED ON AN |
| | ALTERNATIVE UTILITY POLE OR ON A NEW UTILITY POLE TO BE |
| | INSTALLED WITHIN THE RIGHT-OF-WAY. PLEASE NOTE THAT |
| | THIS IS A RESIDENTIAL NEIGHBORHOOD AND SECTION |
| | 78-411(B)(2) STATES THAT WIRELESS FACILITIES SHALL BE |
| | LOCATED ON THE OPPOSITE SIDE OF THE RIGHT-OF-WAY FROM |
| | RESIDENTIAL STRUCTURES AND NOT DIRECTLY IN FRONT OF A |
| | RESIDENTIAL STRUCTURE. |
| | |
| | **** THE CITY'S WIRELESS COMMUNICATION FACILITY |
| | REGULATIONS ARE WRITTEN TO HAVE THE FACILITIES PLACED |
| | IN ARTERIAL RIGHTS-OF-WAY, WHICH ARE TYPICALLY NOT IN |
| | RESIDENTIAL DISTRICTS. IN THE EVENT THAT A POLE IS |
| | PROPOSED FOR A RESIDENTIAL DISTRICT, THE REGULATIONS |
| | STIPULATE THAT THE POLE IS NOT TO BE IN FRONT OF A |
| | HOUSE AND NOT ON THE SAME SIDE OF THE STREET AS |
| | RESIDENTIAL STRUCTURES IF THAT IS AN OPTION. THE |
| | PROPOSED LOCATION DOES NOT MEET EITHER OF THESE |
| | CRITERIA, AND THUS MUST BE RELOCATED. PLEASE NOTE THAT |
| | THIS COMMENT WAS MADE WITH THE ORIGINAL COMMENTS FOR |
| | THIS SITE DATED AUGUST 28, 2019. |
| | |
| | PLEASE REMEMBER THAT POLES SHALL BE LOCATED SO AS TO |
| | ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY AND HAVE |
| | EQUAL SETBACK DISTANCES WITH EXISTING POLES FROM THE |
| | CURBLINE OF THE RIGHT-OF-WAY. |
| | |
| | PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| | DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| | OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| | COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| | THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| | REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| | HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| | THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| | NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| | APPROVED. |
| | |
| | 1) REPEAT COMMENT: PROVIDE A SURVEY, PREPARED BY A |
| | FLORIDA LICENSED SURVEYOR, THAT SHOWS: |
| | |
| | A. THE POLE LOCATION, THE RIGHT-OF-WAY LINE, AND THE |
| | UNDERGROUND ELECTRIC TO THE POLE SO THAT STAFF CAN |
| | VERIFY THAT THE UNDERGROUND ELECTRIC AND ANY REQUIRED |
| | BORE PITS AND HANDHOLES ARE WITHIN THE RIGHT-OF-WAY AND |
| | WHICH JURISDICTION'S RIGHT-OF-WAY THEY ARE IN. |
| | B. THE HEIGHT OF THE PROPOSED POLE AND THE HEIGHT OF |
| | THE UTILITY POLE WITHIN THE RIGHT-OF-WAY THAT IS BEING |
| | USED TO ESTABLISH THE HEIGHT OF THE PROPOSED WIRELESS |
| | COMMUNICATION FACILITY POLE. |
| | C. THE UNDERGROUND UTILITIES FOR THE EXTENT OF THE |
| | PROJECT, INCLUDING THE UNDERGROUND POWER ROUTE. |
| | D. ABOVEGROUND FEATURES, INCLUDING TREES. |
| | E. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES IN |
| | THE AREA TO INCLUDE AN INVENTORY OF THE REGISTRANT'S |
| | EXISTING FACILITIES - NO INFORMATION ON EXISTING |
| | FACILITIES WAS PROVIDED. SHOW THIS INFORMATION ON THE |
| | PLANS AND PROVIDE A NARRATIVE. IF THERE ARE NO |
| | FACILITIES, THIS SHALL BE NOTED ON THE SURVEY. |
| | |
| | **** AN ENGINEER IS NOT PERMITTED TO PREPARE A SURVEY. |
| | **** |
| | |
| | 2) UPDATED REPEAT COMMENT: ENGINEERING PLAN (BASED OFF |
| | THE SURVEY REQUIRED IN COMMENT #1) |
| | |
| | A. SHOW THE UNDERGROUND POWER ROUTE ON THE ENGINEERING |
| | PLAN. **** THIS NEEDS TO BE FOR THE FULL UNDERGROUND |
| | ELECTRIC ROUTE AND BASED ON THE SURVEY. THE POWER |
| | FEEDING SKETCH UPLOADED WITH THE PLAN IS NOT SUFFICIENT |
| | AS IT IS NOT AN ENGINEERING PLAN WITH THE APPROPRIATE |
| | DETAILS. THE CITY REQUIRES THIS INFORMATION AS PART OF |
| | THE WIRELESS COMMUNICATION APPLICATION TO ENSURE THAT |
| | THE BORE IS WITHIN THE RIGHT-OF-WAY. **** |
| | B. PROVIDE THE CROSS SECTION OF THE UNDERGROUND |
| | ELECTRIC SO THAT STAFF CAN VERIFY THAT THE BORE IS DEEP |
| | ENOUGH TO AVOID EXISTING UTILITIES AND DAMAGING THE |
| | ROOT SYSTEMS OF THE TREES OVER THE ELECTRIC PATH. |
| | |
| | 3) THE RESPONSE SHOWS THAT THE METER PLACEMENT FOR THIS |
| | FACILITY IS LOCATED WITHIN A PALM BEACH COUNTY |
| | RIGHT-OF-WAY AND PROVIDES THE PERMIT NUMBER FOR THE |
| | ELECTRIC PERMIT ISSUED BY WEST PALM BEACH. PLEASE NOTE |
| | THAT THE CITY DOES NOT PERMIT FREE STANDING POLE |
| | MOUNTED METERS FOR WIRELESS COMMUNICATION FACILITIES |
| | AND THAT THIS METER DOES NOT MET CITY CONCEALMENT |
| | STANDARDS. THIS METER CONFIGURATION WILL NOT BE |
| | APPROVED FOR FUTURE SITES. |
| | |
| | 4) SINCE NO SURVEY SHOWING THE POLE HIEGHTS, STAFF IS |
| | UNABLE TO VERIFY IF THE POLE HEIGHT COMPLIES WITH CITY |
| | REQUIREMENTS. |
| | |
| | 5) THE CITY STANDARD POLE COLOR AT THIS LOCATION IS |
| | RAL/RAYCAP 7042 TRAFFIC GREY A, OR EQUIVALENT, NOT |
| | SATIN BLACK. |
| | |
| | CONTACT ERIC SCHNEIDER @ 561-822-1446 |
| | [email protected] |
| | |
| | |
| | |
| | |