| Date |
Text |
| 2019-08-22 13:24:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE IS INDICATIONS OF UNDERGROUND WORK. |
| | |
| | PLEASE CLARIFY IF THIS PERMIT IS INTENDED TO COVER ALL |
| | UNDERGROUND WORK AS WELL AS FOR THE ABOVE GROUND |
| | SPRINKLER SYSTEM. |
| | |
| | |
| | |
| | 2) SHEET FP 00 - THE ARE INDICATIONS OF FIRE CODE |
| | REFERENCES; HOWEVER, NFPA 24 IS NOT. |
| | |
| | ALL UNDERGROUND SHALL COMPLY WITH: |
| | |
| | NFPA? 24 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE |
| | SERVICE MAINS AND THEIR APPURTENANCES, 2013 EDITION |
| | |
| | PER # 1 ABOVE IF THIS PERMIT IS INTENDED FOR |
| | UNDERGROUND, PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 3) SHEET FP 00 - THE FIRE HYDRANT IS INDICATED AS BEING |
| | 150' FROM THE FDC. |
| | |
| | PER NFPA 14 |
| | |
| | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| | NOT |
| | MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT |
| | CONNECTED |
| | TO AN APPROVED WATER SUPPLY. |
| | |
| | PLEASE CORRECT OR PROVIDE JUSTIFICATION TO INCREASE |
| | THIS DISTANCE. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF NO SPRINKLERS IN THE DORM |
| | ROOM BATHROOMS AND CLOSETS. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.8 DWELLING UNITS. |
| | 8.15.8.1 BATHROOMS. |
| | 8.15.8.1.1* SPRINKLERS SHALL NOT BE REQUIRED IN |
| | BATHROOMS THAT |
| | ARE LOCATED WITHIN DWELLING UNITS OF HOTELS AND MOTELS, |
| | THAT DO |
| | NOT EXCEED 55 FT2 (5.1 M2) IN AREA, AND THAT HAVE WALLS |
| | AND |
| | CEILINGS OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE |
| | MATERIALS |
| | WITH A 15-MINUTE THERMAL BARRIER RATING, INCLUDING THE |
| | WALLS |
| | AND CEILINGS BEHIND ANY SHOWER ENCLOSURE OR TUB. |
| | 8.15.8.2* CLOSETS AND PANTRIES. SPRINKLERS ARE NOT |
| | REQUIRED IN |
| | CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WITHIN |
| | DWELLING |
| | UNITS IN HOTELS AND MOTELS WHERE THE AREA OF THE SPACE |
| | DOES NOT |
| | EXCEED 24 FT2 (2.2 M2), THE LEAST DIMENSION DOES NOT |
| | EXCEED |
| | 3 FT (0.9 M), AND THE WALLS AND CEILINGS ARE SURFACED |
| | WITH NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE MATERIALS. |
| | |
| | THE CODE DOES NOT EXEMPT PROTECTION OF THESE AREAS IN |
| | DORMITORIES. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |