| Plan Review Notes For Permit 19081001 |
| Permit Number |
19081001 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-10-07 09:45:09 | BUILDING PROVISO | | | REVISED PLANS ADDRESSING THIS ISSUE SHALL BE SUBMITTED | | | AND APPROVED BEFORE FINAL BUILDING INSPECTION PER PHONE | | | CONVERSATION WITH ALAN BIRSE, ARCHITECT. FBC | | | ACCESSIBILITY SECTION 202.4 ALTERATIONS AFFECTING | | | PRIMARY FUNCTION AREAS. DOOR #10 BETWEEN CORRIDOR 811 | | | AND 810 IS REQUIRED TO HAVE 18 INCHES AT THE LATCH ON | | | THE PULL SIDE OF THE DOOR. SEE SECTION 404.2.4.1 FOR A | | | FRONT APPROACH TO THE PULL SIDE OF A SWING DOOR. | | | ANOTHER OPTION WOULD BE TO REMOVE THIS DOOR AND CREATE | | | A CASED OPENING. |
|