2019-09-11 08:58:311ST REVIEW: 19080997
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. WITH AN OCCUPANT LOAD OF 160 ITS REQUIRED TO HAVE
 TWO TOILETS FOR WOMEN AND TWO FOR MEN OR ONE TOILET AND
 ONE URINAL THE MENS BATHROOM CAN NO LONGER BE
 CONSIDERED A SINGLE USER BATHROOM AND WILL NEED THE
 FOLLING MODIFICATION FOR CODE COMPLIANCE.
 A) THE TOILET AND LAVATORY WILL NEED PARTITIONS FOR THE
 ACCESSIBLE STALL AND SHALL COMPLY WITH FBC ACC CH 6 AND
 FBC PL 405.3.4
 B) THE URINAL SHALL HAVE PARTITIONS AND BE OUT SIDE THE
 ACCESSIBLE STALL. PER FBC PL 405.3.5
 C) A LAVATORY IS REQUIRED OUTSIDE THE ACCESSIBLE TOILET
 STALL.PER FBC ACC 213.3.4
  
 2. PROVIDE A WATER ISOMETRIC.PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 4. SHEET A1 PLEASE PROVIDE A DETAIL A LARGER FLOOR PLAN
 OF THE NEW UNISEX RESTROOM AND ELEVATION VIEWS WITH
 DIMENSIONS FOR ROOM, CLEAR FLOOR SPACE, DIMENSIONS FOR
 ALL FIXTURES- HEIGHT FOR THE LAV, WATER CLOSET, MIRROR,
 GRAB BARS, TOILET PAPER DISPENSERS, ETC. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
 604.3.1
 604.3.2.
 606-1-5
 603.3
 609.4
 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  