Plan Review Notes
Plan Review Notes For Permit 19080997
Permit Number 19080997
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-21 14:23:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE INDICATIONS OF CHANGE OF OCCUPANCY AS WELL
 AS ADD ONE UNI-SEX BATHROOM
  
 PLEASE CLARIFY WHAT THE INTENT OF THIS PERMIT IS FOR.
  
  
 2) IF THIS IS A CHANGE OF OCCUPANCY, WHAT IS THE
 PROPOSED OCCUPANCY?
  
 IT APPEARS TO BE A BAR/NIGHCLUB WHICH IS ASSEMBLY IF
 OVER 50 PEOPLE.
  
 PLEASE CLARIFY OCCUPANCY AND PROVIDE A LIFE SAFETY PLAN
 SHOWING ALL DIMENSIONS, OCCUPANCY LOADS, TRAVLE
 DISTANCES, FIRE ALARM AND/OR FIRE SPRINKLERS, EXIT
 SIGNS, EXITS LEADING TO PUBLIC WAYS, EMERGENCY LIGHTS,
 ETC.
  
  
 3) THERE IS AN OFFICE AREA IN THE REAR OF THE
 OCCUPANCY. THE 2ND EXIT FROM THE ASSEMBLY AREA CAN NOT
 PASS THRU THIS OFFICE AREA.
  
 PER NFPA 101
  
 12.2 MEANS OF EGRESS REQUIREMENTS.
 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 CHAPTER 7 AND THIS CHAPTER.
  
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF
 EGRESS.
 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER
 OBJECTS SHALL
 OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE
 FROM, OR
 VISIBILITY THEREOF.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 4) THERE IS AN INDICATION OF A PROPOSED BAR. IS THIS
 PROPOSED BAR PART OF THIS PERMIT? THERE ARE NO DETAILS.
  
 PLEASE CLARIFY AND SEE # 1 & 2 ABOVE, PROVIDE DETAILS
 AS APPLICABLE.
  
  
 5) THERE IS NO DOOR SCHEDULE TO CONFIRM EXIT HARDWARE.
  
 PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WITH
 THE ASSEMBLY CHAPTER(12) OF NFPA 101 AND MEANS OF
 EGRESS (7)
  
  
 6) THERE ARE NO INDICATIONS OF A EXISTING FIRE
 SPRINKLER OF FIRE ALARM SYSTEM.
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AN
 EVALUATION OF CODE COMPLIANT COVERAGE BY A CERTIFIED
 CONTRACTOR.
  
 ANY WORK ON THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE INDICATE EXISTING SYSTEMA AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  