| Date |
Text |
| 2019-08-21 14:23:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE INDICATIONS OF CHANGE OF OCCUPANCY AS WELL |
| | AS ADD ONE UNI-SEX BATHROOM |
| | |
| | PLEASE CLARIFY WHAT THE INTENT OF THIS PERMIT IS FOR. |
| | |
| | |
| | 2) IF THIS IS A CHANGE OF OCCUPANCY, WHAT IS THE |
| | PROPOSED OCCUPANCY? |
| | |
| | IT APPEARS TO BE A BAR/NIGHCLUB WHICH IS ASSEMBLY IF |
| | OVER 50 PEOPLE. |
| | |
| | PLEASE CLARIFY OCCUPANCY AND PROVIDE A LIFE SAFETY PLAN |
| | SHOWING ALL DIMENSIONS, OCCUPANCY LOADS, TRAVLE |
| | DISTANCES, FIRE ALARM AND/OR FIRE SPRINKLERS, EXIT |
| | SIGNS, EXITS LEADING TO PUBLIC WAYS, EMERGENCY LIGHTS, |
| | ETC. |
| | |
| | |
| | 3) THERE IS AN OFFICE AREA IN THE REAR OF THE |
| | OCCUPANCY. THE 2ND EXIT FROM THE ASSEMBLY AREA CAN NOT |
| | PASS THRU THIS OFFICE AREA. |
| | |
| | PER NFPA 101 |
| | |
| | 12.2 MEANS OF EGRESS REQUIREMENTS. |
| | 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | CHAPTER 7 AND THIS CHAPTER. |
| | |
| | 7.1.10 MEANS OF EGRESS RELIABILITY. |
| | 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE |
| | CONTINUOUSLY |
| | MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO |
| | FULL INSTANT |
| | USE IN THE CASE OF FIRE OR OTHER EMERGENCY. |
| | 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF |
| | EGRESS. |
| | 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER |
| | OBJECTS SHALL |
| | OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE |
| | FROM, OR |
| | VISIBILITY THEREOF. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 4) THERE IS AN INDICATION OF A PROPOSED BAR. IS THIS |
| | PROPOSED BAR PART OF THIS PERMIT? THERE ARE NO DETAILS. |
| | |
| | PLEASE CLARIFY AND SEE # 1 & 2 ABOVE, PROVIDE DETAILS |
| | AS APPLICABLE. |
| | |
| | |
| | 5) THERE IS NO DOOR SCHEDULE TO CONFIRM EXIT HARDWARE. |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WITH |
| | THE ASSEMBLY CHAPTER(12) OF NFPA 101 AND MEANS OF |
| | EGRESS (7) |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF A EXISTING FIRE |
| | SPRINKLER OF FIRE ALARM SYSTEM. |
| | |
| | ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AN |
| | EVALUATION OF CODE COMPLIANT COVERAGE BY A CERTIFIED |
| | CONTRACTOR. |
| | |
| | ANY WORK ON THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM |
| | SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. |
| | |
| | PLEASE INDICATE EXISTING SYSTEMA AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |