2019-09-09 08:41:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080997
 ADD: 329-B CLEMATIS ST.
 CONT: BLUE WATER VENTURES OF PALM BEACH
 TEL: 561-339-6128
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY SEPT. 09/ 2019
 ACTION: DENIED
  
 1) PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 NEEDS TO BE CLARIFIED. UNDER THE DESCRIPTION OF WORK
 THE APPLICATION INDICATES A NEW BATHROOM ADDITION WILL
 BE ADDED TO THE BUILDING. THE DEFINITION OF AN ADDITION
 IS AN EXTENSION OR INCREASE IN FLOOR AREA, NUMBER OF
 STORIES OR HEIGHT OF A BUILDING OR STRUCTURE.
 PLEASE NOTE THAT IS NOT THE CASE THE FOOTPRINT IS NOT
 BEING INCREASED, THIS IS AN COMMERCIAL INTERIOR
 REMODEL.
  
 2) SHEET A1:
 2A) SHEET A1 INDICATES THIS IS A CHANGE OF OCCUPANCY.
 IF SO PLEASE INDICATE WHAT THE CHANGE OF OCCUPANCY IS?
 ADDITIONAL INFORMATION IS REQUIRED. IT WOULD APPEAR
 THAT THIS IS STILL AN A2 OCCUPANCY BUT THE CHANGE IS A
 DENSER (MORE OCCUPANTS) AND THE CREATION OF A NEW
 UNISEX RESTROOM. PLEASE CORRECT THE FLOOR PLAN WITH THE
 REMOVAL OF CHANGE IN OCCUPANCY. PLEASE PROVIDE WHAT
 LEVEL OF ALTERATION THIS IS UNDER THE 2017 EXIST.
 BUILD. CODE WORK AREA METHOD OF ALTERATION? EXIST.
 BUILDING CODE SECTION 503-505. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2B) THIS REVIEW ONLY A FLOOR PLAN WAS SUBMITTED, NO
 LIFE SAFETY PLAN WAS SUBMITTED. PLEASE INCLUDE ON THE
 LIFE SAFETY PLAN THE OCCUPANT LOAD BREAK DOWN FOR EACH
 AREA. PLEASE ALSO SHOW THE EXIT ACCESS AISLE, PLEASE
 NOTE NO OCCUPANT LOAD CAN BE TAKEN FOR THE MEANS OF
 EGRESS. TRAVEL DISTANCES. 2 MEANS OF EGRESS SINCE THE
 OCCUPANT LOAD IS 50 OR MORE. PLEASE NOTE THE 2017 FBC-B
 SECTION 1016.2(3) EGRESS THROUGH INTERVENING SPACES
 DOES ALLOW EGRESS THROUGH INTERVENING SPACES AS LONG AS
 THE EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT CAN
 BE LOCKED TO PREVENT EGRESS, THIS ROOM IS BEING
 DECLARED AN OFFICE. IT WOULD APPEAR THE LIFE SAFETY
 CODES NFPA MAYBE THE STRICTER OF THE 2 CODES. WHEN
 THERE IS A DISCREPANCY IN THE CODES, THE STRICTER OF
 THE 2 CODES SHALL RULE.
  
 2C) THE OTHER ISSUE THAT THE FIRE SAFETY CODE (NFPA)
 WILL RULE ON IS THE WIDTH OF THE EGRESS PATH FOR THE
 OCCUPANT LOAD DECLARED. THE 2017 FBC-B GIVES UNDER THE
 SECTION 1005.3.2 SIZING OR REQUIRED CAPACITY BASED ON
 THE OCCUPANT LOAD, FACTOR OF 0.2 INCH PER OCCUPANT.
 SECTION 1018.2 GIVES MINIMUM CLEAR WITH FOR B & M
 OCCUPANCIES. SECTION 1018.2 AISLES IN ASSEMBLY SPACES,
 AISLES AND AISLE ACCESS BUT THIS IS FOR TABLE AND
 CHAIRS, NOT FOR STANDING ONLY. AGAIN THE FIRE SAFETY
 CODES (NFPA) WILL BE THE STRICTER OF THE 2 CODES AND
 GOVERN THE ACCESS AISLE WIDTHS.
  
 3) SHEET A1 PLEASE PROVIDE A DETAIL A LARGER FLOOR PLAN
 OF THE NEW UNISEX RESTROOM AND ELEVATION VIEWS WITH
 DIMENSIONS FOR ROOM, CLEAR FLOOR SPACE, DIMENSIONS FOR
 ALL FIXTURES- HEIGHT FOR THE LAV, WATER CLOSET, MIRROR,
 GRAB BARS, TOILET PAPER DISPENSERS, ETC. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
 604.3.1
 604.3.2.
 606-1-5
 603.3
 609.4
 604.7
  
 4A) PLEASE NOTE THE BAR DOES NOT SHOW A DROPPED SECTION
 FOR A PERSON IN A WHEEL CHAIR AND COMPLIANCE WITH:
 2017 ACCESS. CODE 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
  
 4B)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  