Plan Review Notes
Plan Review Notes For Permit 19080990
Permit Number 19080990
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-21 15:29:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 SPECIFIES ROOF REPAIR. PROVIDE A COMPLETE DESCRIPTION
 OF THE REPAIRS THAT ARE TO BE DONE. MARK THE AREAS THAT
 WILL BE REPAIRED ON A ROOF DIAGRAM AND SPECIFY THE
 APPROXIMATE SQUARE FEET OF EACH OF THE AREAS. FBC
 107.2.1 FBC EXISTING BUILDING 706.1.1 NOT MORE THAN 25
 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION OF ANY
 EXISTING BUILDING SHALL BE REPAIRED OR REPLACED IN ANY
 12 MONTH PERIOD UNLESS THE ENTIRE EXISTING ROOFING
 SYSTEM OR SECTION IS REPLACED.
  
 2) ON THE PRODUCT APPROVAL FOR THE MODIFIED BITUMEN
 ROOFING MARK THE SYSTEM TYPE AND DESIGN PRESSURE FOR
 THE SYSTEM THAT YOU WISH TO INSTALL. FBC 107.2.1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved