| Plan Review Notes For Permit 19080979 |
| Permit Number |
19080979 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-29 06:38:31 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY WHICH ONE OF THE SYSTEMS AND ITS MAXIMUM | | | DESIGN PRESSURE LISTED IN THE PRODUCT APPROVAL FOR THE | | | GAF SELF-ADHERING MODIFIED NOA NO 16-1206.02 WILL BE | | | INSTALLED. YOU CAN CIRCLE THESE ITEMS ON THE PRODUCT | | | APPROVAL. | | | | | | 2) THIS PROJECT IS A ONE STORY SINGLE FAMILY RESIDENCE | | | LOCATED IN EXPOSURE C WITH A 170 MPH VULT WIND SPEED. | | | NONE OF THE MAXIMUM DESIGN PRESSURES LISTED IN THE NOA | | | ARE ADEQUATE FOR ROOF ZONES 2 AND 3 WITHOUT ENHANCED | | | FASTENING. SEE GENERAL LIMITATION #7 WHICH REQUIRES | | | SIGNED AND SEALED RAS 117 CALCULATIONS. FBC-R 905.11.3 | | | | | | |
|