| 2019-09-10 15:43:31 | RESIDENTIAL (R3) SITE WALL REVISION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- MASTER PERMIT 18120193 IS A DIGITAL SUBMITTAL. PLANS |
| | SUBMITTED ARE PRINTED COPIES. PRINTED COPIES OF DIGITAL |
| | SIGNATURES ARE NOT CONSIDERED SIGNED AND SEALED. SEE |
| | SEC. 61G15-23.004 FAC FOR PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | DRAWINGS NEED TO BE UPLOADED AND HAVE DIGITAL |
| | SIGNATURE. PLEASE CONTACT THE LIBRARIANS FOR DIGITAL |
| | SUBMITTAL. |
| | |
| | LAURA ELIZABETH MARCHANT |
| | PLANS REVIEW LIBRARIAN |
| | DEVELOPMENT SERVICES |
| | BUILDING INSPECTIONS |
| | PHONE: 805-6700 EXT: 6658 |
| | E-MAIL: [email protected] |
| | |
| | OR |
| | |
| | |
| | CAROLINE PUELL |
| | PLANS REVIEW LIBRARIAN |
| | DEVELOPMENT SERVICES |
| | BUILDING INSPECTIONS |
| | PHONE: 805-6700 EXT: 6659 |
| | E-MAIL: [email protected] |
| | |
| | |
| | IMPORTANT REMAINDERS: |
| | |
| | *****(1)PERMIT WAS APPROVED WITH PROVISO. PROVIDE |
| | REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. SEE PROVISO BELOW: |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO (SUBMIT |
| | INFORMATION PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS): |
| | 1-REVISE PLANS AND RESUBMIT FOR REVIEW. SHOW ATTIC |
| | ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN THE 1ST & 2ND |
| | FLOOR. |
| | 2-SUBMIT PRODUCT APPROVALS FOR REVIEW: A)WINDOW |
| | MULLIONS AND SPECIFY MULLION SIZE. B)DOORS PRODUCT |
| | APPROVAL FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE |
| | SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| | SCHEDULE. C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: |
| | CLEARLY MARK WHICH ASSEMBLY L IS GOING TO BE USED. D) |
| | SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. E) WATER PROOFING AT |
| | TERRACE. PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO |
| | RECEIVE MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. |
| | F) DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| | APPROVALS. |
| | 3-SUBMIT COMPLETE INFORMATION FOR ALUMINUM TRELLIS |
| | UNDER SEPARATE PERMIT PER ARCHITECT'S RESPONSE LETTER. |
| | 4-REVISE PLANS AND RE-SUBMIT FOR REVIEW: ENTRY FOYER |
| | FINISH ELEVATION IN ALL PLANS. PER JOHN MELHORN, THE |
| | ELEVATION WILL BE 9'-0" (NAVD OF 1988) NOT 8'-6". |
| | 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS. |
| | PROVIDE PRODUCT APPROVAL AND REVISE PLANS FOR REVIEW |
| | SHOWING LOCATION. ALSO, POWDER ROOM LOCATED IN THE |
| | GARAGE NEEDS TO BE ELEVATED TO 9'-0". |
| | |
| | |
| | *****(2)PROPERTY IS LOCATED IN FLOOD ZONE AE. ELEVATION |
| | CERTIFICATES ARE REQUIRED FOR BUILDING UNDER |
| | CONSTRUCTION AND FINISHED CONSTRUCTION. THERE ARE NO |
| | CITY RECORDS FOR THE BUILDING UNDER CONSTRUCTION |
| | ELEVATION CERTIFICATE. NEED TO PROVIDE ELEVATION |
| | CERTIFICATE FOR BUILDING UNDER CONSTRUCTION. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |