| Plan Review Notes For Permit 19080921 |
| Permit Number |
19080921 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-20 06:58:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF THE PRODUCT APPROVALS FOR THE TU | | | PLUS PEEL AND STICK UNDERLAYMENT THAT IS SPECIFIED IN | | | THE PROPOSAL. THE PROPOSED INSTALLATION FOR THIS | | | PROJECT USES A ROOF TILE ADHESIVE. BE SURE THAT THE | | | PRODUCT APPROVAL YOU SUBMIT IS COMPATIBLE WITH ADHESIVE | | | SET TILE AND HAS THE UPLIFT PRESSURES SPECIFIED. FBC | | | 107.2.1 & FAC RULE 61G20 | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING. FBC | | | 107.2.1 THE SLOPE IS 5/12 PER THE PROPOSAL. |
|