| 2019-08-20 11:10:59 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 3103.1 GENERAL. THE PROVISIONS OF SECTIONS 3103.1 |
| | THROUGH 3103.4 SHALL APPLY TO STRUCTURES ERECTED FOR A |
| | PERIOD OF LESS THAN 180 DAYS. TENTS AND OTHER MEMBRANE |
| | STRUCTURES ERECTED FOR A PERIOD OF LESS THAN 180 DAYS |
| | SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE. |
| | THOSE ERECTED FOR A LONGER PERIOD SHALL COMPLY WITH |
| | APPLICABLE SECTIONS OF THIS CODE. |
| | |
| | *ADDITIONAL REQUIREMENTS |
| | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| | OF 30 FEET OR GREATER IN ANY DIRECTION: |
| | |
| | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| | BASEPLATE/TIEDOWN DETAILS. |
| | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| | |
| | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| | A DESIGN PROFESSIONAL. |
| | |
| | OPTION TO ABOVE REQUIREMENT ? |
| | YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT |
| | WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH |
| | |
| | |