| Plan Review Notes For Permit 19080882 |
| Permit Number |
19080882 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-09-06 16:54:36 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PER THE SIGNED AND SEALED LETTER FROM THE ENGINEER, THE | | | ROOF TILE THAT THEY WISH TO USE DOES NOT HAVE A PRODUCT | | | APPROVAL. IN ORDER TO USE THAT ROOF TILE, THE ENGINEER | | | WILL HAVE TO SUBMIT A SIGNED AND SEALED RATIONAL | | | ANALYSIS COMPARING THE PROPOSED ROOF TILE WITH A | | | SIMILAR TILE THAT HAS A CURRENT PRODUCT APPROVAL. TWO | | | SETS OF THE ENGINEERED DOCUMENTS ARE REQUIRED. THE | | | PROPOSED TILE WILL NEED TO HAVE SIMILAR DIMENSIONS AND | | | SHAPE. THE WEIGHT OF THE PROPOSED TILE WILL HAVE TO BE | | | EQUAL OR GREATER THAN THE TILE WITH THE PRODUCT | | | APPROVAL. WHEN THE ENGINEERING IS REVIEWED AND APPROVED | | | YOU WILL BE GIVEN ONE SET OF THE DOCUMENTS THAT WILL BE | | | STAMPED AS APPROVED TO HAVE IN THE FIELD FOR THE | | | BUILDING INSPECTOR. FBC 107.2.1.2 |
|