Plan Review Notes
Plan Review Notes For Permit 19080828
Permit Number 19080828
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-09-19 15:17:18THE FOLLOWING COMMENTS WERE NOT ADDRESSED DURING THIS
 SUBMISSION CYCLE:
  
 1. ADDRESS TO BE CORRECTED ON COVER SHEET. - COMPLIED
 10/23/19
 2. ACCESS CONTROL RISER DIAGRAM INDICATED ACS 14 & 15,
 WHILE PALN SHOWS ACS 15 & 16. - COMPLIED 10/23/19
 3. NO SPEC SHEET PROVIDED FOR KEY OVERRIDE SWITCH
 (HONEYWELL 4005K801) - COMPLIED 10/23/19
  