| 2019-09-07 09:35:23 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19080808 |
| | ADD: 314 FLAMINGO DRIVE |
| | CONT: PEDRO FURTADO |
| | TEL: 818-620-7860 |
| | E-MAIL: DAMONMONTYDMAC.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. SEPT. 07/2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.01 MISSING INFORMATION. 2017 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATIVE CODE, 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | UNDER WHICH BUILDING CODE WERE THE PLANS DEVELOPED |
| | SITE REQUIREMENTS: |
| | PARKING |
| | DRIVING/TURNING RADIUS |
| | FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| | SET BACK/SEPARATION |
| | WATER LINES AND SEWER LINES |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED CHAPTER 4 FBC-B |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED, NO |
| | SQ. FOOTAGE OF OCCUPANCIES ON PLANS, |
| | NOR TOTAL SQUARE FOOTAGE |
| | RATING OF FIRE BARRIER ASSEMBLIES, VERTICAL AND |
| | HORIZONTAL |
| | BUILDING FIRE SPRINKLERED OR NOT, FIRE SPRINKLER PLANS |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | SITE REQUIREMENTS/ ACCESSIBLE ROUTE |
| | TOILET AND BATHING FACILITIES/ KITCHENETTE |
| | DRINKING FOUNTAINS |
| | |
| | 2) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER WHAT |
| | BUILDING CODE THESE PLANS WERE DEVELOPED. STATEWIDE THE |
| | 2017 FAMILY OF FLORIDA BUILDING CODES WERE ADOPTED ON |
| | DEC. 31/ 2017. UPDATE PLANS. |
| | |
| | 3) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER THE |
| | 2017 FLORIDA EXISTING BUILDING CODE WHAT METHOD THE |
| | PLANS WERE DEVELOPED. FOR THIS REVIEW THE REVIEWER WILL |
| | BE USING BOTH THE 2017 FBC-B AND THE 2017 EXIST. |
| | BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY SECTION |
| | 1001.2.2. CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN |
| | OCCUPANCY CLASSIFICATION. |
| | |
| | THIS BUILDING WE COULD NOT FIND A BUSINESS TAX RECEIPT |
| | / BUT PALM BEACH COUNTY PROPERTY APPRAISERS HAS THE |
| | OCCUPANCY TYPE LISTED AS WAREHOUSE/ STORAGE. THAT IS |
| | WHY WE ARE LISTING THIS REVIEW AS A CHANGE IN |
| | OCCUPANCY/ CHANGE IN USE. |
| | |
| | 4A) PLEASE SHOW COMPLIANCE WITH THE 2017 EXIST. BUILD. |
| | CODE SECTION 1002.1 COMPLIANCE WITH THE BUILDING CODE. |
| | WHERE THE CHARACTER OR USE OF AN EXISTING BUILDING OR |
| | PART OF AN EXISTING BUILDING IS CHANGED TO ONE OF THE |
| | FOLLOWING SPECIAL USE OR OCCUPANCY CATEGORIES AS |
| | DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, THE |
| | BUILDING SHALL COMPLY WITH ALL OF THE APPLICABLE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING: |
| | 406.3.MOTOR VEHICLE-RELATED OCCUPANCIES. |
| | EXIST BLDG. CODE 406.4.6 MIXED OCCUPANCY SEPARATION. |
| | PARKING GARAGES SHALL BE SEPARATED FROM OTHER |
| | OCCUPANCIES IN ACCORDANCE WITH SECTION 508.1 OF THE |
| | FBC-B. WHERE A BUILDING CONTAINS MORE THAN ONE |
| | OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL |
| | COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2, |
| | 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS. |
| | PLEASE NOTE PARKING GARAGES ARE PART OF THE SPECIALTY |
| | OCCUPANCIES FOUND IN CHAPTER 4 AND WILL REQUIRE FIRE |
| | SEPARATION AS PER TABLE 508.4 OF THE FBC-B. PLEASE ALSO |
| | NOTE FOOTNOTE B. THE REQUIRED SEPARATION FROM AREAS |
| | USED ONLY FOR PRIVATE OR PLEASURE VEHICLES SHALL BE |
| | REDUCED BY 1 HOUR BUT NOT LESS THAN 1 HOUR. OPENING |
| | PROTECTIVES FOR DOORS CAN BE FOUND UNDER THE FBC-B |
| | TABLE 716.5. PRIVATE GARAGES UNDER 1,000 SQ. IS TO BE |
| | CONSIDERED AN U OCCUPANCY (UTILITY). IN THE 2017 FBC-B |
| | 406.3.1 THE CLASSIFICATION FOR A PRIVATE GARAGE AS |
| | UTILITY STILL REQUIRES A 1 HOUR FIRE BARRIER IN |
| | COMPLIANCE WITH SECTION 707 OF THE FBC-B. |
| | |
| | 4B) PLEASE NOTE THAT PRIVATE GARAGES NEED ONLY TO |
| | COMPLY WITH 406.3.1 THROUGH 406.3.6. VENTILATION |
| | REQUIREMENTS FOUND UNDER 406.6.2 ARE NOT REQUIRED! |
| | |
| | 5A) THE IDEA OF CALLING THIS STRUCTURE A LIVE/ WORK |
| | UNIT DOES NOT MEET THE CRITERIA FOUND IN SECTION |
| | 419.1.1 LIMITATIONS OF THE 2017 FBC-B. THE |
| | NON-RESIDENTIAL AREA IS PERMITTED TO BE NOT GREATER |
| | THAN50 % OF THE AREA OF EACH LIVE/ WORK UNITS. |
| | |
| | 5B) THE OTHER OCCUPANCY SEPARATION THAT WILL NEED TO |
| | OCCUR IS THE RESIDENTIAL R-3 VERSES THE A-3 OCCUPANCY |
| | (GALLERY). TABLE 508.4 OF THE 2017 FBC-B WILL ALSO |
| | REQUIRE A 1 HOUR FIRE SEPARATION PER TABLE 508.4 FOR A |
| | SPRINKLERED BUILDING. |
| | |
| | 6) THE OCCUPANCY TYPE HAD NOT BEEN DECLARED BUT WITH AN |
| | AREA OF 1,250 S. F. / 30= 42 OCC. FOR THE GALLERY, |
| | LIBRARY 344 S. F. / 30= 12 OCC. AND STORAGE 236 S. F. / |
| | 300= 1 OCC. FOR A TOTAL OF 50 OCCUPANTS. THIS WOULD |
| | REQUIRE 2 EGRESS DOORS, BOTH THE GALLERY AND LIBRARY |
| | DOORS CAN SERVE THIS PURPOSE BUT WILL NEED TO SHOW EXIT |
| | LIGHTS OVER THESE DOORS IN COMPLIANCE WITH THE 2017 |
| | FBC-B SECTION 1108.2. PLEASE ALSO DEVELOP A LIFE SAFETY |
| | PLAN SHOWING MEANS OF EGRESS, COMMON PATH OF TRAVEL, |
| | AND OCCUPANT LOADS ON THE LIFE SAFETY PLAN. |
| | |
| | 7) IN THE 2017 EXIST. FBC SHOW COMPLIANCE WITH SECTIONS |
| | 1012.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1012.2.1 |
| | AND 1012.2.2. |
| | |
| | |
| | 7A) EXIST. BUILD. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS OR |
| | WHERE THERE IS A CHANGE OF OCCUPANCY WITHIN A SPACE |
| | WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM |
| | THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA |
| | BUILDING CODE, BUILDING THAT REQUIRES AN AUTOMATIC FIRE |
| | SPRINKLER SYSTEM TO BE PROVIDED BASED ON THE NEW |
| | OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA |
| | BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED |
| | THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY |
| | OCCURS. |
| | |
| | |
| | 7B) EXIST. BUILD. CODE 1012.2.2 FIRE ALARM AND |
| | DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| | CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| | OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| | FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| | 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| | A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE |
| | FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW |
| | CONSTRUCTION. |
| | |
| | 8) PLEASE SHOW HOW COMPLIANCE WITH THE 2017 EXIST. |
| | BUILD. CODE SECTION 1012.1.4 WILL BE ACHIEVED. 1012.1.4 |
| | ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| | 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT |
| | UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION |
| | SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | NOTICE: 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 8A) WHEN STRUCTURES ARE ALTERED, AND OR GO THROUGH A |
| | CHANGE OF OCCUPANCY THE BUILDING IS LOOKED AT FOR |
| | ACCESSIBILITY ISSUES. NEW CONSTRUCTION ELEMENTS HAVE TO |
| | COMPLY WITH ACCESSIBILITY. EXISTING ELEMENTS THAT DO |
| | NOT COMPLY ONLY 20 % OF THE CONTRACT VALUE (THAT MAY |
| | INCREASE DEALING WITH CODE ISSUES THAT HAVE TO BE |
| | BROUGHT UP TO CODE). THE PLANS WERE SUBMITTED WITH A |
| | CONSTRUCTION VALUE OF $75,000 DOLLARS OF VALUE, TO |
| | BRING ACCESSIBLE ELEMENTS UP TO CODE UP TO AN |
| | ADDITIONAL $15,000.00 MAY HAVE TO BE SPENT AND IN THIS |
| | ORDER. |
| | 2017 FBC- ACCESS. CODE. 202.4.2 ACCESSIBLE FEATURES IN |
| | THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF |
| | ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE |
| | ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO |
| | THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL |
| | SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE |
| | MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE |
| | COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE |
| | ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE |
| | ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | EITHER THE DESIGNER OF RECORD OR CONTRACTOR ON THEIR |
| | LETTERHEAD CAN SUBMIT A BREAK DOWN WHERE THESE FUNDS |
| | ARE TO BE SPENT IN THE CASE ALL OF THE ACCESSIBLE |
| | ELEMENTS CANNOT BE FIXED WITH THE STATED DOLLAR AMOUNT |
| | GIVEN. THE REMAINDER OF THE ACCESSIBLE ELEMENTS THAT |
| | WERE NOT CORRECTED CAN BE LEFT AS IS, THE |
| | DISPROPORTIONALITY HAS BEEN MET. |
| | |
| | 8B) THE PLANS WILL NEED TO SHOW THAT THERE IS AN |
| | ACCESSIBLE ENTRANCE AND BECAUSE THE REQUIREMENT FOR 2 |
| | EXITS BOTH DOORS FROM THE GALLERY/ LIBRARY WILL NEED TO |
| | SHOW THEY ARE AT GRADE AND ACCESSIBLE. |
| | |
| | 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 8C) PLEASE NOTE THE SHEET A1.01 DOES NOT SHOW |
| | RESTROOMS, DRINKING FOUNTAINS NOR A SERVICE SINK IN THE |
| | GALLERY / LIBRARY OCCUPANCY. THE FLOOR PLAN A1.01 DOES |
| | NOT SHOW ANY RESTROOMS WITHIN THE GALLERY / LIBRARY |
| | OCCUPANCY. PLEASE PROVIDE THE OCCUPANT LOAD AND |
| | COMPLIANCE WITH THE 2017 FBC-EXIST. BUILD. 1010.1 |
| | REVIEW 1010.6 AND IN THE 2017 FBC-B SECTIONS 2902.1.1, |
| | 2902.2 AND TABLE 2902.1 TO SHOW ACCESSIBLE DRINKING |
| | FOUNTAINS & RESTROOMS. |
| | |
| | 8D) THE FLOORPLAN FOR THE RESIDENTIAL UNIT SHOWS A |
| | RESTROOM, WATERCLOSET AND LAV ONLY PLEASE SHOW WHAT |
| | SIZE THE POCKET DOOR IS TO THE RESTROOM. 2017 |
| | ACCESSIBILITY CODE 233.3.6 IF ONLY A TOILET ROOM IS |
| | PROVIDED AT GRADE LEVEL, SUCH TOILET ROOM SHALL HAVE A |
| | CLEAR OPENING OF 29 INCHES. |
| | |
| | 8E) THE FLOOR PLAN A1.1 DOES NOT SHOW A DRINKING |
| | FOUNTAIN. PLEASE PROVIDE COMPLIANCE WITH 2017 FBC- |
| | ACCESS. CODE SECTION 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 9) THE FLOOR PLAN A.1.1. SHOWS IN THE R-3 OCCUPANCY A 2 |
| | STORY UNIT WITH ENCLOSED STAIRWAY ON THE 1ST FLOOR |
| | LEADING DIRECTLY TO THE EXTERIOR. WHAT THE PLAN DOES |
| | NOT INDICATE IF THE STAIRWAY IS 1 HOUR FIRE RATED |
| | WALLS? |
| | PLEASE PROVIDE OF WHAT MATERIALS THE STAIRWELL WALLS |
| | ARE MADE OF? 2017 EXIST. BUILD. CODE: |
| | 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| | CATEGORY. |
| | |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | EXCEPTION 4 DEALS WITH RATED CORRIDOR WALLS BUT THE |
| | SAME CAN BE USED FOR STAIRWELL WALLS. THE OTHER ISSUE |
| | IS UNDER THE STAIRWELL THE PLANS SHOW A RESTROOM AND |
| | WASHER/ DRYER ROOM. WHAT ARE THESE WALLS AND CEILING |
| | MADE OF? |
| | EXCEPTIONS: |
| | 4. EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH SIDES OF |
| | WOOD LATH AND PLASTER IN GOOD CONDITION OR 1/2- |
| | INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE |
| | PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE |
| | UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR |
| | EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT |
| | ABOVE. |
| | |
| | 10) SHEET A.1.1 SHOWS A NEW STOREFRONT DOORS AND GARAGE |
| | DOOR PLEASE PROVIDE COMPLIANCE WITH: |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,OVERHEAD GARAGE DOOR |
| | (B) WINDOWS AND MULLIONS (POSSIBLE SIDELIGHTS) |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 14) SHEET A1.1 WITH NEW EXTERIOR DOORS WE WILL NEED TO |
| | HAVE THE WIND DESIGN CRITERIA. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 14.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| | GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 14.2. RISK CATEGORY. |
| | |
| | 14.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 14.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 14.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 15) CITY AND COUNTY RECORDS INDICATE THIS STRUCTURE WAS |
| | BUILT IN 1964 WHEN ASBESTOS WAS USED IN CONSTRUCTION. |
| | IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO |
| | ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY |
| | TO COMPLY WITH THE STATE & FEDERAL ASBESTOS |
| | REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61- |
| | NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS |
| | SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: * |
| | DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 355-3070 |
| | |
| | 16) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| | BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| | THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| | WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| | PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 / FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |