| Plan Review Notes For Permit 19080792 |
| Permit Number |
19080792 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-26 10:03:47 | THIS SHOULD HAVE BEEN A PLUMBING REVIEW AND NOT GAS. | | 2019-08-23 07:08:06 | 8/23/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH | | | COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE | | | DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS | | | MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED | | | CORRECTIONS. | | | | | | 1) ALL GAS AND SPA HEATERS SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER | | | APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z | | | 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL | | | NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2017 | | | FBC-ENERGY ? SEC. R403.10.4 | | | | | | 2) HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY | | | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT | | | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR | | | OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC- | | | ENERGY- SEC. R 403.10.3. | | | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|