| 2019-09-06 16:06:04 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19080775 |
| | REVIEWED: SEPTEMBER 6, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 301.2(7)FIGURE FBC[R]PROVIDE WIND DIAGRAM THAT |
| | MATCHES THE ROOF CONDITION OF THIS HOUSE. |
| | |
| | 2) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO |
| | KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| | PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU |
| | CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| | PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING |
| | STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION |
| | CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB |
| | LIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| | |
| | 3) [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE |
| | DRAINAGE PLAN. SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| | STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF |
| | COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE |
| | GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES |
| | WITHIN THE FIRST 10 FEET. EXCEPTION: WHERE LOT LINES, |
| | WALLS, SLOPES OR OTHER PHYSICAL BARRIERS PROHIBIT 6 |
| | INCHES OF FALL WITHIN 10 FEET (3048 MM), DRAINS OR |
| | SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY |
| | FROM THE STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET |
| | OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| | 2 PERCENT AWAY FROM THE BUILDING. |
| | - |
| | |
| | 4) 403.1.7.3 FBC[R] FOUNDATION ELEVATION. ON GRADED |
| | SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND |
| | ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF |
| | DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A |
| | MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE |
| | ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE |
| | BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT |
| | REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY |
| | FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE |
| | SITE. |
| | |
| | 5) 703.4 FBC[R] PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| | BE USED TO MEET REQUIREMENTS OF R703.4 |
| | |
| | 6) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| | REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| | THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| | INDEX AND SMOKE DEVELOPED INDEX. |
| | |
| | 7) INDICATE THE ROOF TILE ATTACHMENT METHOD THAT WILL |
| | BE USED BY MARKING THE APPROPRIATE INFORMATION ON THE |
| | PRODUCT APPROVAL. FBC 107.2.1 IF AN ADHESIVE WILL BE |
| | USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC 107.3.4 |
| | IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE PRODUCT |
| | APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT WILL MEET |
| | WINDLOADS. |
| | |
| | 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | SLIDING GLASS DOOR, ARCH WINDOWS AND MULL BETWEEN, OR |
| | INDICATE THAT YOU WOULD LIKE IT DEFERRED. |
| | |
| | 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | TILE ROOFING ADHESIVE, OR INDICATE THAT YOU WOULD LIKE |
| | IT DEFERRED. |
| | |
| | PROVISOS: |
| | DEFERRED SUBMITTALS - ROOF TRUSS SHOP DWGS TO INSPECTOR |
| | PRIOR TO INSTALLATION. |
| | PROVIDE ROOFING (TILE) ATTACHMENT OR INDICATE THAT IT |
| | WILL BE DEFERRED UNTIL ROOFING SUB PERMIT IS APPLIED |
| | FOR. |
| | SEPARATE PERMITS REQUIRED FOR- |
| | DRIVEWAY |
| | FENCING |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | - PROVISOS WILL BE ADDED TO THE PLANS AT FINAL |
| | STAMPING. |
| | |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |