| Plan Review Notes For Permit 19080773 |
| Permit Number |
19080773 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-21 10:38:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | 1. GARAGE DOOR OPENER GFCI RECEPTACLES NOT READILY | | | ACCESSIBLE. NEC 210.8 | | | 2. NO DISCONNECTS SHOWN FOR AC C/U?S OUTSIDE. FBC | | | 107.2.1 | | | 3. ALL BALCONIES REQUIRE MINIMUM 1 GFCI PROTECTED | | | RECEPTACLE NEC 210.53E3 | | | 4. SMOKE/CO ALARMS REQUIRED PER FBC RE 314&315 | | | 5. TWO ATS?S SHOWN ON RISER DIAGRAM BUT ONLY ONE SHOWN | | | ON PLAN, PLEASE PROVIDE CORRECTION. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|