| 2019-10-01 15:52:01 | GAS PROVISO | | | 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA | | | SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR ALL GAS | | | EQUIPMENT AND REGULATORS. THE DOCUMENTS SHALL BE | | | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL | | | INSPECTION. PROCEED AT YOUR OWN RISK. | | | 2. LOCATION OF POOL HEATER ON PLAN SHEET A100 WAS | | | REQUESTED BUT NOT ADDRESSED. IT IS UNCLEAR AS TO HOW | | | THE ENGINEER WAS ABLE TO DETERMINE DISTANCE FROM METER | | | TO THE POOL HEATER IN ORDER TO CALCULATE PIPE SIZES. | | | INSPECTOR TO VERIFY DISTANCE ON ROUGH AND FINAL | | | INSPECTION. PROCEED AT YOUR OWN RISK | | | |
|