| 2019-09-16 13:14:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1. PLEASE NOTE THAT REQUESTS HAVE BEEN MADE FOR CHANGES |
| | TO ARCHITECTURAL DRAWINGS AS WELL AS MEP. THESE |
| | REQUESTS MUST BE SATISFIED PRIOR TO GAS PERMIT |
| | APPROVAL. |
| | 2. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET |
| | A001, THE LOCATIONS OF THE GAS METER, THE GENERATOR AND |
| | THE POOL HEATER. |
| | 3. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET A100 |
| | AND ON PLAN SHEET P2.1 AN ACCESS PANEL (INCLUDE |
| | DIMENSIONS OF PANEL) TO ACCOMMODATE THE ABOVE CEILING |
| | REGULATOR SERVING THE FIREPLACE IN ACCORDANCE WITH FBC |
| | FG 410.1. |
| | 4. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR SLEEVED |
| | AND VENTED PE PIPE INSTALLED BELOW A HARD SURFACE. |
| | ADDITIONALLY, WHEN LANDSCAPE/HARDSCAPE DRAWINGS ARE |
| | SUBMITTED, PER WPB FBC 107.2.1, LOCATIONS OF SLEEVED |
| | AND VENTED PIPE SECTIONS SHALL BE INDICATED. |
| | 5. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. FIREPLACE |
| | (40,000 BTUH) IS SHOWN AT THE LOCATION THAT INDICATES A |
| | POOL HEATER (400,000 BTUH) ON PLAN SHEET P2.1. PER WPB |
| | FBC 107.2.1, PLEASE CLARIFY. |
| | 6. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. PER WPB |
| | FBC 107.2.1, CLEARLY SHOW ON THE ISOMETRIC DRAWING THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE IN ACCORDANCE WITH |
| | FBC FG SECS. 402.4.1, 402.4.2. OR FBC RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | 7. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON |
| | P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION |
| | THE DISTANCE FROM THE POINT OF DELIVERY, (GAS METER / |
| | REGULATOR) TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND / OR SYSTEM FOR EACH PRESSURE SYSTEM (2 PSI/0.5 |
| | PSI) IN ACCORDANCE WITH FBC FG SEC.402.4.1, 402.4.2, OR |
| | FBC RES SEC. G 2413.4.1, G2413.4.2. |
| | 8. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON |
| | P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION |
| | THE TYPE OF GAS (LP OR NATURAL). IT IS ASSUMED TO BE NG |
| | DUE TO NOTE ON GAS ISOMETRIC PERTAINING TO NATURAL GAS |
| | CONNECTION BUT NEEDS TO BE STATED. |
| | 9. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC FG SEC. 402.2, AND 301.3 OR 2017 FBC |
| | RES SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. |
| | 10. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION IN ACCORDANCE WITH |
| | FBC FG SEC.410.1, FBC RES SEC. G2421.1. RE: FBC FG |
| | 410.3; INDICATE ON SUBMITTALS FOR INDOORS THE TYPE OF |
| | VENT ELIMINATOR IS TO BE USED OR PROVIDE ON THE PLANS, |
| | VENT PIPING (MATERIAL TYPE, SIZE AND ROUTING) TO THE |
| | EXTERIOR WITH DETAIL OF EXTERIOR TERMINATION IN |
| | ACCORDANCE WITH FBC FG IN ACCORDANCE WITH FBC FG SECS. |
| | 502 THRU 505 OR FBC RES SEC.G2426 THROUGH G2439. |
| | 11. PER WPB FBC 107.2.1, IN ADDITION TO THE COMBUSTION |
| | AIR CALCULATIONS PROVIDED FOR THE DRYER ON PLAN SHEET |
| | M0-2, SUBMIT COMBUSTION AIR CALCULATIONS FOR THE |
| | ADDITIONAL INDOOR GAS APPLIANCES. WHERE COMBUSTION AIR |
| | IS PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR IN ACCORDANCE WITH FBC FG SEC.304.9.3 |
| | OR FBC RES G2407.9.3. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |