| 2019-10-02 11:04:32 | 1) THE PLANS THAT HAVE BEEN SUBMITTED ARE FROM THE |
| | INITIAL GAS REVIEW UNDER PERMIT #19050833 FOR THE |
| | GENERATOR AND DO NOT SHOW THE ADDED POOL HEATER OM THE |
| | GAS DRAWING.THESE PLANS CANNOT BE USED FOR THIS |
| | REVISION AS THIS PERMIT HAS ALREADY BEEN ISSUED. SUBMIT |
| | TWO COPIES OF A GAS DRAWING THAT SHOWS ALL THE GAS |
| | APPLIANCES/ EQUIPMENT THAT ARE CONNECTED TO THIS GAS |
| | SYSTEM. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | 2) 1) SUBMIT TWO COPIES OF THE INSTALLATION |
| | INSTRUCTIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON THE |
| | SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| | 2) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS STEEL TUBING ON THE PLANS. 2ND REQUEST. |
| | 3) THE PLANS SHOW THE CSST LINE AS A LOW PRESSURE LINE |
| | BUT THERE IS NO GAS REGULATOR SHOWN ON THE LINE AND THE |
| | LINE IS SHOWN CONNECTED TO THE 2 PSI PIPING.. CLARIFY. |
| | 3) UNIONS ARE REQUIRED WITHIN ONE FOOT UPSTREAM OR |
| | DOWNSTREAM OF THE PRESSURE REGULATORS. FGC SEC. 410.2 |
| | (7). |
| | 4) SUBMIT THE APPLICABLE SIZING TABLES FOR THE LOW |
| | PRESSURE SECTIONS OF THE GAS SYSTEM. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |