Plan Review Notes
Plan Review Notes For Permit 19080722
Permit Number 19080722
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-30 17:36:111ST REVIEW: 18080722
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE DIMENSIONS OF BATHROOM. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHOW THE CLEAR FLOOR FOR TOILET SHALL COMPLY WITH
 FBC ACC 604.3.1
  
 3. LABEL ALL CLEAR FLOOR SPACES WITH DIMENSIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHOW COMPLIANCE OF THE BREAK ROOM SINK SHALL COMPLY
 WITH FBC ACC 606.2-3
  
 5. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. FBS ACC 609.4
  
 6. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 7. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE.PER FBC ACC 604.5.2
  
 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR.PER FBC ACC 604.7
  
 9. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES \ MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION,PER FBC
 ACC 604.2
  
 10. THE DIMENSIONS FOR THE LAVATORY AND THE MIRROR
 PLEASE CLARIFY. PER FBC ACC 603.3, 606.2-3
  
 11. SHT P1.1 THE BREAK ROOM SINK SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP PER FBC PL 912.1 ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 12. UNDER THE DOMESTIC WATER SERVICE NOTES #2 #3 LIST
 2014 CODE THE THE CORRECT CODE SHALL BE 2017. PER WPB
 AMEND TO FBC 107.2.1
  
 13. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]