| Date |
Text |
| 2019-08-20 14:57:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | 2. SITE PLAN SHOWING LAYOUT OF EQUIPMENT AND PIPING IS |
| | NOT LEGIBLE. PER WPB FBC 107.2.1, PROVIDE LEGIBLE SITE |
| | PLAN WITH LAYOUT SHOWING LOCATION OF TANK AND RANGE. |
| | TANK SHALL BE LOCATED IN ACCORDANCE WITH NFPA 58 |
| | SECTION 6.4.4.1. |
| | 3. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, SECTION 6.4.4.1. |
| | 4. PROVIDE COPY OF HOUSE PLAN SHOWING LOCATION OF RANGE |
| | AND TANK AND PIPE ROUTING. |
| | 5. PROVIDE RISER DIAGRAM SHOWING ALL HORIZONTAL AND |
| | VERTICAL DIMENSIONED INTERVALS FROM TANK TO RANGE. SIZE |
| | IN ACCORDANCE WITH FBC FG 402.4 SIZING TABLES OR NFPA |
| | 58 CHAPTER 16 SIZING TABLES. SHOW ALL VALVES AND |
| | REGULATORS. IDENTIFY ABOVE GROUND TO UNDERGROUND AND |
| | THROUGH THE WALL TRANSITIONS. IDENTIFY 10 PSI AND |
| | 12-13? WC SECTIONS. SHOW TYPE OF MATERIAL BEING USED. |
| | INDICATE TYPE OF GAS. |
| | 6. THE SUBMITTED REGULATOR(S) DOES/DO NOT MATCH THE |
| | INFORMATION PROVIDED. PLEASE CLARIFY. |
| | 7. THE SUBMITTED VESSEL (HORIZONTAL CONFIGURATION) DOES |
| | NOT MATCH UP TO THE VERTICAL CONFIGURATION OF THE |
| | ANCHORING DETAILS (SHEET T-1). PLEASE CLARIFY. PLEASE |
| | INDICATE ON SUBMITTAL FOR ABOVE OR BELOW GROUND USE AND |
| | HIGHLIGHT SIZE. |
| | 8. PROVIDE ENGINEER?S DIGITAL SIGNATURE WITH PROPER 3RD |
| | PARTY VERIFICATION ON SHEET T-1. |
| | 9. REFERENCE SIZING TABLE(S) SPECIFY TYPE K & L COPPER |
| | TUBING OR ACR. HIGHLIGHT OR POINT TO THE APPLICABLE |
| | DISTANCE. |
| | 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | RANGE PER FBC FG SEC.304.1 |
| | 11. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG |
| | SEC. 402.2. |
| | 12. PER WPB FBC 107.2.1, IF USING COPPER, PROVIDE AN |
| | AFFIDAVIT THAT THE GAS BEING CONVEYED DOES NOT CONTAIN |
| | MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN SULFIDE |
| | PER 100 STANDARD CU. FT. OF GAS TO SHOW COMPLIANCE WITH |
| | FBC FG 403.4.3. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19080717 1273 SLASH PINE CIR |
| | |