| 2023-05-22 14:57:54 | ELEVATION CERTIFICATE - REVIEW COMMENTS |
| | |
| | 5TH REVIEW: 2010 FBC |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING- (SOME OF THE PREVIOUS COMMENTS HAVE |
| | NOT BEEN CORRECTED) |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | THE ELEVATION CERTIFICATE THAT WAS SUBMITTED IS DENIED |
| | FOR THE FOLLOWING REASONS: |
| | NOTE: THIS ADDITION WAS PERMITTED WHEN THE FIRM MAP |
| | DATED MARCH 1, 1979 WAS IN EFFECT. THE VERTICAL DATUM |
| | ON THE FIRM WAS IN NGVD AND THE CITY'S FLOOD ORDINANCE |
| | REQUIRED A 6 INCH FREE BOARD ABOVE THE BFE. |
| | |
| | 1) RESOLVED. |
| | |
| | 2) RESOLVED. |
| | |
| | 3) RESOLVED. |
| | |
| | 4) NOT RESOLVED. [ THE NOTE ABOUT THE STORAGE AREA IN |
| | THE COMMENTS FOR SECTION D, SHOULD STATE THAT THE |
| | STORAGE AREA IS BELOW THE DFE AND HAS (3) THREE |
| | ENGINEERED FLOOD VENTS WITH 1200 SQ IN OF TOTAL NET |
| | AREA OF FLOOD OPENINGS. YOU WILL ALSO NEED TO REVISE |
| | THE NUMBER OF ENGINEERED FLOOD OPENINGS TO (5) FIVE FOR |
| | THE ATTACHED GARAGE WITH A TOTAL NET FLOOD OPENINGS |
| | AREA OF 2000 SQ IN.] SECTION A9(A) OF THE ELEVATION |
| | CERTIFICATE INCORRECTLY HAS THE SQUARE FOOTAGE OF THE |
| | GARAGE AS 1477 SQFT. AND THE LAST REVISED PLAN DATED |
| | 03/30/2023 (REV#5) HAS THE GARAGE (1105 SF) AND THE |
| | ATTACHED STORAGE AREA (504 SF) FOR A TOTAL OF 1609 SF. |
| | BOTH OF THESE AREAS ARE WET FLOOD PROOFED. REVISE THE |
| | E.C. TO INCLUDE BOTH AREAS. |
| | |
| | |
| | 5) RESOLVED. |
| | |
| | 6) RESOLVED. |
| | |
| | 7) RESOLVED. |
| | |
| | 8) RESOLVED. |
| | |
| | 9) RESOLVED. |
| | |
| | 10) NOT RESOLVED. [ THE PHOTOS ARE NOT LABELED |
| | CORRECTLY AND ARE NOT DATED. SEE THE INSTRUCTIONS NEAR |
| | THE TOP OF THE BUILDING PHOTOGRAPHS PAGE. THE |
| | PHOTOGRAPHS ARE TO BE IDENTIFIED WITH THE DATE TAKEN |
| | AND LABELED "FRONT VIEW", "REAR VIEW", "RIGHT SIDE |
| | VIEW" AND "LEFT SIDE VIEW".] TO THE EXTENT POSSIBLE, |
| | THE PHOTOGRAPHS SHOULD SHOW THE ENTIRE BUILDING. THE |
| | PHOTOS ARE REQUIRED TO BE IN COLOR AND SHOW THE FLOOD |
| | VENTS. |
| | |
| | 11) NOT RESOLVED. [ THE ELEVATION OF THE GARAGE FLOOR |
| | IS 5.45' NGVD ON THE FINAL SURVEY AND THE ELEVATION |
| | CERTIFICATE HAS 4.0' NAVD OR 5.5' NGVD. THE ELEVATIONS |
| | NEED TO MATCH.] SUBMIT A FINAL SURVEY WITH BUILDING |
| | ELEVATIONS. THE ELEVATIONS ON THE SURVEY AND THE |
| | ELEVATION CERTIFICATE MUST MATCH. RENAME THE GYM AS |
| | STORAGE TO MATCH THE REVISED PLAN. |
| | |
| | 12) NOT RESOLVED. [ THE INSTRUCTIONS REQUIRE THE |
| | STATE'S ABBREVIATION OF FL IN THE BOX. ] IN SECTION B3. |
| | OF THE ELEVATION CERTIFICATE THE STATE'S TWO (2) LETTER |
| | ABBREVIATION (FL) SHOULD BE ENTERED AND NOT SPELLED |
| | OUT. |
| | |
| | 13) NOT RESOLVED. [ PLEASE CORRECT.] ALL ITEMS IN |
| | SECTIONS A8. A), B) & C) SHOULD BE N/A INSTEAD OF 0 PER |
| | THE INSTRUCTIONS. |
| | |
| | ALL OF THESE REQUIREMENTS ARE LOCATED IN THE 2019 |
| | EDITION OF FEMA'S ELEVATION CERTIFICATE AND |
| | INSTRUCTIONS AND IN FEMA TECHNICAL BULLETINS. |
| | |
| | |
| | |
| 2023-05-22 14:28:04 | |
| | |
| | |