| Plan Review Notes For Permit 19080692 |
| Permit Number |
19080692 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-15 18:10:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: 2010 FBC ELEVATION CERTIFICATE | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THE ELEVATION CERTIFICATE THAT WAS SUBMITTED IS DENIED | | | FOR THE FOLLOWING REASONS. | | | 1) PER THE APPROVED BUILDING PLANS, THERE IS AN | | | ATTACHED GARAGE THAT IS BELOW THE REQUIRED DESIGN FLOOD | | | ELEVATION WITH FLOOD VENTS. UNDER ITEM A9 THERE IS NO | | | ATTACHED GARAGE OR FLOOD OPENINGS LISTED. | | | 2) THIS PROJECT WAS PERMITTED WHEN THE PREVIOUS FLOOD | | | MAPS WERE IN EFFECT AND THE ELEVATIONS ON THE APPROVED | | | PLANS ARE NGVD RATHER THAN NAVD. PROVIDE NOTE AND | | | CONVERSION FACTOR IN THE COMMENT SECTION. | | | 3) THE TOP OF THE BOTTOM FLOOR SHOULD BE THE ATTACHED | | | GARAGE. THE NEXT HIGHER FLOOR SHOULD BE THE FIRST FLOOR | | | OF THE RESIDENCE. THE LOWEST ELEVATION OF MACHINERY IS | | | REQUIRED TO BE AT 7.5 FT NGVD OR 6.0 FT NAVD. | | | 4) THE PHOTOGRAPHS ARE REQUIRED TO SHOW THE FLOOD | | | VENTS. | | | | | | |
|