| Plan Review Notes For Permit 19080683 |
| Permit Number |
19080683 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-01-15 18:46:40 | APPROVED UNDER MASTER 17110874 | | | | | | GAS PROVISO UNDER MASTER: | | | | | | 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR | | | ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW | | | WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS | | | NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE | | | MANUFACTURE WILL BE REQUIRED STATING THAT THIS | | | CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION | | | PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE | | | LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE | | | REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE | | | MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING | | | LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO | | | FUNCTION PROPERLY SIMULTANEOUSLY. | | | | | | PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW | | | ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND | | | EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE | | | LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE | | | REQUESTED DIMENSIONS ON THE PLAN. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|